D Category Options and Descriptions

D01 Board Communication Alarm An alarm is triggered when a carrier communication module malfunction is detected. Default setting: Do Not Disturb Mode.

Options
RS-485 Numbers
備註

On

1

Do Not Disturb

2

Default

After selecting a command, confirm whether to Save or Not Save.

D02 Pipe Sensor Alarm Alarm - A1: Triggers an alarm when the pipe diameter sensing module malfunctions. Default setting: Do Not Disturb Mode.

Options
RS-485 Numbers
Remarks

On

1

Do Not Disturb

2

Default

After selecting a command, confirm whether to Save or Not Save.

D03 Bad Signal Alarm Alarm - C3: Triggers an alarm when the ultrasonic signal is poor. Default setting: Do Not Disturb Mode.

Options
RS-485 Numbers
Remarks

On

1

Do Not Disturb

2

Default

After selecting a command, confirm whether to Save or Not Save.

D04 Off-Pipe Alarm Alarm - A4: Triggers an alarm when the flow meter is not correctly installed on the pipe.

  • Default Do Not Disturb Mode: Red light will not flash, but when the alarm is triggered, flow is reset to zero, and alarm A04 is set to 1.

  • On: Red light flashes, flow is reset to zero, and alarm A04 is set to 1 when triggered.

Options
RS-485 Numbers
Remarks

On

1

Do Not Disturb

2

Default

After selecting a command, confirm whether to Save or Not Save.

D05 FlowLIM Ala. (Flow Volume Limit Alarm) Alarm - B: Triggers an alarm when instantaneous flow exceeds the defined range. Can be turned off. Default: Off.

Options
RS-485 Numbers
Remarks

Off

0

Default

On

1

Do Not Disturb

2

After selecting a command, confirm whether to Save or Not Save.

D06 Up LIM (Upper Limit) Defines the upper limit of the normal flow range for D04.

Parameter Input Range
Values

Data Type

float32

Default

100

Minimum

-99999

Maximum

100000

After selecting a command, confirm whether to Save or Not Save.

D07 Low LIM (Lower Limit) Defines the lower limit of the normal flow range for D04.

Parameter Input Range
Values

Data Type

float32

Default

0

Minimum

-100000

Maximum

99999

After selecting a command, confirm whether to Save or Not Save.

D08 Hysteresis% (Hysteresis Percentage) Sets the percentage of hysteresis for clearing flow upper/lower limit alarms. The percentage is defined as a portion of the range between the upper and lower limits.

  • Range: 0–33%.

  • Default: 3%.

  • Must be a positive value.

Parameter Input Range
Values

Data Type

int

Default

3

Minimum

0

Maximum

10

After selecting a command, confirm whether to Save or Not Save.

D09 Total Ala. (Total Alarm) Alarm - B: Triggers an alarm when the cumulative flow exceeds the defined range. Can be turned off. Default: Off.

Options
RS-485 Numbers
Remarks

Off

0

Default

On

1

Do Not Disturb

2

After selecting a command, confirm whether to Save or Not Save.

D10 Total Trig. (Total Alarm Trigger Condition) Defines the trigger condition for the cumulative target value (D11), such as whether the value exceeds or falls below the target. Default: Greater Than Target.

Options
RS-485 Numbers
Remarks

Higher than target

0

Default

Lower than target

1

After selecting a command, confirm whether to Save or Not Save.

D11 Total Target Defines the cumulative target value.

Parameter Input Range
相應數值

Data Type

float32

Default

100

Minimum

-999,999,999

Maximum

999,999,999

After selecting a command, confirm whether to Save or Not Save.

D12 Iout Alarm Alarm - B: Triggers an alarm when the output current exceeds the 4–20 mA range. Can be turned off. Default: Off.

Options
RS-485 Numbers
Remarks

Off

0

Default

On

1

Do Not Disturb

2

After selecting a command, confirm whether to Save or Not Save.

D13 Speed Alarm Alarm - B: Triggers an alarm when the absolute value of flow velocity exceeds 6 m/s. Default: On.

Options
RS-485 Numbers
Remarks

Off

0

On

1

Default

Do Not Disturb

2

After selecting a command, confirm whether to Save or Not Save.

D14 PulseOverlap Alarm Alarm - B: Indicates pulse output signal overlap due to an excessively large parameter setting in E03. Can be turned off. Default: On.

Options
RS-485 Numbers
Remarks

On

1

Default

Do Not Disturb

2

After selecting a command, confirm whether to Save or Not Save.

D15 IoutStatAla (Iout Status Alarm) Defines the alarm mode for Iout status. Options: On, Off, and Do Not Disturb.

  • Default: Do Not Disturb Mode, where screen colour and LED indicators remain unchanged during an abnormality, but the status is displayed in the communication section and status page.

Options
RS-485 Numbers
Remarks

On

1

Do Not Disturb

2

Default

After selecting a command, confirm whether to Save or Not Save.

D16 Dosing Alarm Manually adjusts the dosing alarm mode. Options: Off, On, and Do Not Disturb. Default: Off.

Options
RS-485 Numbers
Remarks

Off

0

Default

On

1

Do Not Disturb

2

After selecting a command, confirm whether to Save or Not Save.

Last updated