FU-ES EchoSense Instruction Manual
  • ⚠Safety Instructions
  • This instruction manual version is v1.0
    • Manual Update Log
  • Measurement principle and usage scenario
    • Firmware Update Date and Version Feature Description
  • Warranty
  • Exterior, Specs, Model
  • Installation and Setup
    • Mechanism Installation
    • Mechanical and Electrical iInstallation
    • Parameter setup
      • Z02 Automatic Pipe Size Detection Guide
  • Human Machine Interface
    • Introduction of human machine interface
    • Hybrid Page Setup and Usage Interface Guide
    • Monitoring Screen
    • Simulation Mode
    • Data interpretation on monitoring screens
    • Password input page
    • Setup screen
  • Communication
    • OCT output
    • Analog current output (0-20mA, 4-20mA)
    • RS485 and Modbus RTU Setting
    • Modbus RTU Protocol
      • Read-only memory read instruction(04) and memory lists
      • Read-Write Memory List
      • Read/Write Memory Read Command (03)
      • Read-write memory single Register write instruction(06)
      • Read/Write Memory Dual-Register Write Command (30)
      • Read/Write Memory Four-Register Write Command (31)
      • Single Bit Data Read/Write Commands (01/05) (Commonly Used in HMIs)
  • Parameters Table
    • Z Category Options and Descriptions
    • A Category Options and Descriptions
      • A02 Preset Pipe Specification Table for Different Models
      • A03 ~ A07 Data Range Explanation Based on Model Specifications
    • B Category Options and Descriptions
    • K Category Options and Descriptions
    • C Category Options and Descriptions
    • D Category Options and Descriptions
    • E Category Options and Descriptions
    • F Category Options and Descriptions
    • H Category Options and Descriptions
    • Pagasfsae 1
    • Page 1
  • Alarm and description of system conditions
  • Troubleshootings and Abnormalities
    • Iout 4-20/0-20mA debug process
    • OCT Alarm Debug Process
    • OCT Pulse Debug Process
    • RS485 Debug Process
  • Certification
  • FU-ES Product Page
  • LORRIC English Website
  • LORRIC Integration and Application Center
Powered by GitBook
On this page
Export as PDF
  1. Troubleshootings and Abnormalities

OCT Pulse Debug Process

PreviousOCT Alarm Debug ProcessNextRS485 Debug Process

Last updated 2 years ago

Environment and Parameter Check

  1. Confirm if the power supply works fine.

  2. Confirm whether the confirmation page data is consistent with the communication data.

  3. Confirm that the OCT function is enabled and defined correctly (parameter ), if E02 uses pulse v2.

  4. Confirm that the OCT preset state is on "NC" or off "NO" (parameter ).

  5. Confirm that the circuit wiring is correct, the external power supply connection and power supply work fine, the unused wiring is insulated, and there is no magnetic field interference in the surrounding area.

Hardware, Wiring, and Program of the Receiver Check

  1. Please confirm that the value and unit of E14 (Pulse unit) are the same as those required by the receiver program. For details, please refer to the description of the parameter table.

  2. Use the current gear of the three-purpose ammeter to connect between OCT+ and the positive pole of the power supply, and confirm whether there is current flowing when C0=1. Or use the voltage range to confirm whether there is a voltage difference close to the power supply voltage between OCT+ and OCT- when S0=1. If it is found that there is no correct output for the first time, please reconfirm the power supply circuit.

Results and Actions

  1. The OCT output is normal, and the receiving end equipment and program are also normal. If the data is still abnormal, confirm other causes of the abnormality (pipe size, flow rate).

  2. The main unit of this device may be damaged. If you have other units at hand, you can conduct a cross test to confirm that the receiving device, data processing program or line are all normal.

  3. Record the serial number of the fuselage, the wiring diagram (all flowmeter-related wiring) and the model brand of the receiving end, and contact the original factory.

  4. Please confirm whether there is any abnormality in the receiving device, data processing program or line.

Users need to refer to the actual situation, detailed troubleshooting, please contact LORRIC.

Enter parameter , you can set the number of pulse output per second, please confirm at the receiving end whether you have received the corresponding data, especially whether the number is normal.

Please confirm that the parameter (Pulse width) is greater than or equal to the minimum pulse duration requirement of the receiving device.

Enter the parameter to test the receiving end. In the setting screen, if you set open, it will not conduct, and if you set conduct, it will conduct.

E02
E01
F03
E03
F04