FU-ES EchoSense Instruction Manual
  • ⚠Safety Instructions
  • This instruction manual version is v1.0
    • Manual Update Log
  • Measurement principle and usage scenario
    • Firmware Update Date and Version Feature Description
  • Warranty
  • Exterior, Specs, Model
  • Installation and Setup
    • Mechanism Installation
    • Mechanical and Electrical iInstallation
    • Parameter setup
      • Z02 Automatic Pipe Size Detection Guide
  • Human Machine Interface
    • Introduction of human machine interface
    • Hybrid Page Setup and Usage Interface Guide
    • Monitoring Screen
    • Simulation Mode
    • Data interpretation on monitoring screens
    • Password input page
    • Setup screen
  • Communication
    • OCT output
    • Analog current output (0-20mA, 4-20mA)
    • RS485 and Modbus RTU Setting
    • Modbus RTU Protocol
      • Read-only memory read instruction(04) and memory lists
      • Read-Write Memory List
      • Read/Write Memory Read Command (03)
      • Read-write memory single Register write instruction(06)
      • Read/Write Memory Dual-Register Write Command (30)
      • Read/Write Memory Four-Register Write Command (31)
      • Single Bit Data Read/Write Commands (01/05) (Commonly Used in HMIs)
  • Parameters Table
    • Z Category Options and Descriptions
    • A Category Options and Descriptions
      • A02 Preset Pipe Specification Table for Different Models
      • A03 ~ A07 Data Range Explanation Based on Model Specifications
    • B Category Options and Descriptions
    • K Category Options and Descriptions
    • C Category Options and Descriptions
    • D Category Options and Descriptions
    • E Category Options and Descriptions
    • F Category Options and Descriptions
    • H Category Options and Descriptions
    • Pagasfsae 1
    • Page 1
  • Alarm and description of system conditions
  • Troubleshootings and Abnormalities
    • Iout 4-20/0-20mA debug process
    • OCT Alarm Debug Process
    • OCT Pulse Debug Process
    • RS485 Debug Process
  • Certification
  • FU-ES Product Page
  • LORRIC English Website
  • LORRIC Integration and Application Center
Powered by GitBook
On this page
  • Specs
  • Cable wiring
  • Parameter setup
  • Pulse output
Export as PDF
  1. Communication

OCT output

PreviousCommunicationNextAnalog current output (0-20mA, 4-20mA)

Last updated 2 years ago

Specs

Please see the page of .

Cable wiring

Please see the page of .

Parameter setup

Please refer to the .

Set-up steps as below:

  1. Please set up the first.

  2. Connect cable first according to the cable wiring instructions on this page.

  3. Set up parameter E01 for selecting NC(Normal Close) or NO(Normal Open) when there is no signal.

  4. Set up parameter E02 for specifying output signal content.

    1. For selecting “pulse output”

      1. Use E03 to confirm each pulse width.

      2. Use F03 to simulate specific pulse output frequency at OCT for testing with external devices.

    2. For selecting “pulse v2”

      1. Use E03 to confirm each pulse width.

      2. Use E14 to determine each pulse capacity.

      3. F03 to simulate specific pulse output frequency at OCT for testing with external devices.

    3. For selecting “out of range flow volume notice”.

      1. Use D05 to turn on the alarm.

      2. Use D06 D07 for specifying normal flow range.

      3. Use D08 for specifying hysteresis range percentage. D07 is a positive value, it means the single range must exceed in order to disable the alarm.

      4. Set up F01 and F02 to simulate flow volume and go back to the monitoring screen to confirm if the alarm works.

      5. Turn off the simulation mode.

    4. For selecting “Total Alarm.” (“Inform of over total target”)

      1. Use D09 to turn off alarm.

      2. Use D10 for specifying notification conditions. "Larger Than" is for positive flow direction, "Less Than" is for negative flow direction.

      3. Use D11 for specifying total target, positive number is for positive flow, negative number is for negative flow.

      4. Set up F01 and F02 to simulate flow volume and go back to the monitoring screen to confirm the alarm works.

      5. Turn off the simulation mode.

  5. Go back to the monitoring screen, finish.

Pulse output

The user uses parameter E13 to select a volume first, and the device outputs a digital square wave every time it accumulates through a specified volume.

the monitoring screen
mechanical and electrical installation
parameter set-up page
basic parameters