Read-Write Memory List

Large numerical values read or written in different formats (float32/int64) may exhibit a variance below 1/10,000. In read commands, the register length must not exceed 20 registers. Commands exceeding this length will be disregarded. More refer to the list for details.

Usage Instructions for the Read-Write Memory List

Field Name

Function

Reg Location

Specifies the location of the read-write memory, distinct from the read-only memory space.

Reg Length

Defines the data length of the register variable.

Memory Content Name

Provides a description of the memory content.

Data Format

Specifies the format used for data transmission and reception.

Read Command

Indicates availability for read commands.

Write Command

Indicates availability for write commands. Certain register positions marked with "X" do not support remote writing.

Classification Option List Link

Links to detailed items under each category menu.

Read-Write Memory List

Reg Location
Reg Lengt
Memory Content Name
Data Format
Read Command
Write Command
Classification Option List Link

A parameter Category

00 00

1

A02 Preset Pipe Spec

int16

03

More refer to the list for details

00 01

1

A03 Pipe Geo Unit

int16

03

06

More refer to the list for details

00 02

2

A04 Pipe Outer Diameter

float32

03

More refer to the list for details

00 04

2

A05 Pipe Perimeter

float32

03

More refer to the list for details

00 06

2

A06 Pipe Thickness

float32

03

More refer to the list for details

00 08

2

A07 Pipe Inner Diameter

float32

03

More refer to the list for details

00 0A

1

A08 Pipe Material

int16

03

More refer to the list for details

00 0B

2

A09 Pipe Soundspeed

float32

03

More refer to the list for details

00 0D

1

A10 Liquid Type

int16

03

More refer to the list for details

00 0E

2

A12 Liquid Soundspeed

float32

03

More refer to the list for details

00 10

2

A13 K Viscosity cst

float32

03

More refer to the list for details

00 12

1

A15 Damping

int16

03

06

More refer to the list for details

00 13

1

A16 Direction

int16

03

06

More refer to the list for details

00 14

1

A17 Neg Flow

int16

03

06

More refer to the list for details

00 15

2

A18 Low Flow Cutoff

float32

03

30

More refer to the list for details

00 17

1

A19 Fast Update

int16

03

06

More refer to the list for details

00 18

1

A20 Anti Noise

int16

03

06

More refer to the list for details

00 19

2

A23 Zero Offset

float32

03

30

More refer to the list for details

00 1B

1

A24 Start up check

int16

03

06

More refer to the list for details

00 1C

1

A25 Off-pipe zero

int16

03

06

More refer to the list for details

00 1D

1

A26 Beta Mode

int16

03

06

More refer to the list for details

B parameter Category

01 00

1

B01 Vol Unit

int16

03

06

More refer to the list for details

01 01

1

B02 Time Unit

int16

03

06

More refer to the list for details

01 02

1

B03 Total Unit

int16

03

06

More refer to the list for details

01 03

1

B04 VelocityUnit

int16

03

06

More refer to the list for details

01 04

1

B05 Dec Place

int16

03

06

More refer to the list for details

01 05

1

B06 Pipe Geo Unit

int16

03

06

More refer to the list for details

K parameter Category

0A 00

1

K02 Calibra Mode

int16

03

06

More refer to the list for details

0A 01

2

K03 Scale Factor

float32

03

30

More refer to the list for details

0A 03

2

K04 Manual Offset

float32

03

30

More refer to the list for details

0A 05

2

K05 Totalizer Scale

float32

03

30

More refer to the list for details

C parameter Category

02 00

1

C01 Total Method

int16

03

06

More refer to the list for details

02 01

1

C02 Del Total

int16

03

06

More refer to the list for details

02 02

1

C03 Dosing Mode

int16

03

06

More refer to the list for details

02 03

2

C04 Dosing Target

float32

03

30

More refer to the list for details

02 05

1

C05 Dosing Reset Time

int16

03

06

More refer to the list for details

02 83

4

C04 Dosing Target(64)

int64

03

31

More refer to the list for details

D parameter Category

03 00

1

D01 BoardComm Ala

int16

03

06

More refer to the list for details

03 01

1

D02 Pipe Sensor Alarm

int16

03

06

More refer to the list for details

03 02

1

D03 Bad UltraS Signal

int16

03

06

More refer to the list for details

03 03

1

D04 Off Pipe Alarm

int16

03

06

More refer to the list for details

03 04

1

D05 FlowLIM Ala

int16

03

06

More refer to the list for details

03 05

2

D06 Up LIM

float32

03

30

More refer to the list for details

03 07

2

D07 Low LIM

float32

03

30

More refer to the list for details

03 09

1

D08 Hysteresis%

int16

03

06

More refer to the list for details

03 0A

1

D09 Total Ala

int16

03

06

More refer to the list for details

03 0B

1

D10 Total Trig

int16

03

06

More refer to the list for details

03 0C

2

D11 Total Target

float32

03

30

More refer to the list for details

03 0E

1

D12 Iout Alarm

int16

03

06

More refer to the list for details

03 0F

1

D13 Speed Alarm

int16

03

06

More refer to the list for details

03 10

1

D14 PulseOverlap

int16

03

06

More refer to the list for details

03 11

1

D15 IoutStatAla

int16

03

06

More refer to the list for details

03 12

1

D16 Dosing Alarm

int16

03

06

More refer to the list for details

03 8C

4

D11 Total Target(64)

int64

03

31

More refer to the list for details

E parameter Category

04 00

1

E01 NC/NO

int16

03

06

More refer to the list for details

04 01

1

E02 OCT Info

int16

03

06

More refer to the list for details

04 02

1

E03 Pulse Width

int16

03

06

More refer to the list for details

04 03

1

E06 Iout Def

int16

03

06

More refer to the list for details

04 04

2

E07 4mA Value

float32

03

30

More refer to the list for details

04 06

2

E08 20mA Value

float32

03

30

More refer to the list for details

04 08

1

E09 Iout Error

int16

03

06

More refer to the list for details

04 09

2

E11 4mA Adj uA

float32

03

30

More refer to the list for details

04 0B

2

E12 20mA Adj uA

float32

03

30

More refer to the list for details

04 0D

1

E13 Iout Range

int16

03

06

More refer to the list for details

04 0E

1

E14 PulseV2 Unit

int16

03

06

More refer to the list for details

04 0F

1

E17 Endianness

int16

03

06

More refer to the list for details

F parameter Category

05 00

2

F01 Sim Volume

float32

03

30

More refer to the list for details

05 02

1

F02 Sim Mode

int16

03

06

More refer to the list for details

H parameter Category

07 00

1

H01 LED Bri

int16

03

06

More refer to the list for details

07 01

1

H02 LCD Bri

int16

03

06

More refer to the list for details

07 02

1

H03 Green Light

int16

03

06

More refer to the list for details

07 03

1

H04 Language

int16

03

06

More refer to the list for details

07 04

1

H06 Reset

int16

03

06

More refer to the list for details

07 05

1

H07 Lock Device

int16

03

06

More refer to the list for details

07 06

1

H08 Password

int16

03

06

More refer to the list for details

07 07

1

H09 Home Page

int16

03

06

More refer to the list for details

07 08

1

H10 Debug Page

int16

03

06

More refer to the list for details

Last updated