OCT output
Specifications
NPN, PNP Output
Power Supply
5-30V 200mA
Reverse Polarity Protection
Yes
Wiring
NPN, PNP
Current Consumption
200 mA @ 12V during stable operation at startup (excluding communication current)
Wiring
OCT NPN Output Wiring Diagram
Brown: 24 VDC (+), Blue: 0 VDC (–), Orange: OCT Output (+), Yellow: OCT Output (−)
The OCT output circuit operates with a loop power of 5–30 VDC, 200 mA. This function requires the brown and blue lines of the main DC power supply to be powered. For clarity, the DC power lines are omitted from this diagram. Refer to the DC Power Wiring Diagram for details.

OCT PNP Output Wiring Diagram
Brown: 24 VDC (+), Blue: 0 VDC (−), Orange: OCT Output (+), Yellow: OCT Output (−)
The OCT output circuit operates with a loop power of 5–30 VDC, 200 mA. This function requires the brown and blue lines of the main DC power supply to be powered. For clarity, the DC power lines are omitted from this diagram. Refer to the DC Power Wiring Diagram for details.

OCT Parameter Configuration
Follow the steps below to configure OCT output parameters:
Set Basic Parameters
Refer to the Parameter Settings page and complete the following steps: Language Setting, Pipe Settings — A02: Pipe Standard, A04: Pipe Outer Diameter, A06: Pipe Wall Thickness, A08: Pipe Material
Execute Z03 (Automatic Initialization).
E02 OCT Definition (Output Signal Type)
Set parameter E02 OCT Info to specify the output signal type.
If "Pulse Output" is selected:
Use E03 Pulse Width to set the duration of each pulse.
Use F03 to simulate the pulse output and verify that the receiving end correctly receives the pulse count.
If "Pulse V2" is selected:
Use E03 Pulse Width to set the duration of each pulse.
Use E14 Pulse V2 Unit to define the volume represented by each pulse.
Use F03 to simulate the pulse output and verify that the receiving end correctly receives the pulse count.
If "Total Alarm" is selected:
Use D09 Total Alarm to enable the alarm.
Use D10 Total Trig. to set the trigger condition:
"Greater than Target" for forward flow
"Less than Target" for reverse flow
Use D11 Total Target to specify the cumulative target:
Positive value for forward flow
Negative value for reverse flow
If "Flow Alarm" is selected:
Use D05 FlowLIM Alarm to enable the flow range alarm.
Use D06 UP LIM (Upper Limit) and D07 Low LIM (Lower Limit) to define the normal flow range.
Note: If either D06 or D07 is adjusted, the other must also be set; otherwise the display may not function correctly. If both are unset, default values are D06 = 100, D07 = 0.
Use D08 Hysteresis to define the hysteresis operation method. Values must be positive and expressed as a percentage; larger values reduce repeated alarm triggers.
Note 1
Note 2
Last updated