FP-AS510 Paddle Wheel Flowmeter Instruction Manual
  • ⚠Safety instructions
  • This instruction manual version is v1.0
  • Measure principle and usage scenario
  • Warranty
  • Exterior, Spec, Model
    • Device
    • Paddle set
    • T-connector
  • Install and set-up
    • Mechanism installation
    • Mechanical and electrical installation
    • Parameter setup
  • Human machine interface
    • Introduction of human machine interface
    • Monitoring screen
    • Data interpretation on monitoring screens
    • Setup screen
  • Communication
    • OCT output
    • 4-20mA
    • RS485
    • Modbus RTU Protocol
      • Read-only memory read instruction(04) and memory lists
      • Read-write memory list
      • Read-write memory read instruction(03)
      • Read-write memory single Register write instruction(06)
      • Read-write memory double Register write instruction(30)
  • Parameters Table
  • Alarm and description of system conditions
  • Trouble and abnormality shooting
  • Certification
  • FP-AS510 Product Page
  • LORRIC English Website
  • LORRIC Integration and Application Center
Powered by GitBook
On this page
  • SPEC
  • Cable wiring
  • Parameter setup

Was this helpful?

Export as PDF
  1. Communication

4-20mA

PreviousOCT outputNextRS485

Last updated 4 years ago

Was this helpful?

SPEC

Please see the page of

Cable wiring

Please see the page of

Parameter setup

Please refer to the

Set-up steps as below:

  1. Connect cable first according to the cable wiring section on this page.

  2. Set up parameter E06 for selecting the data to output.

  3. Parameter E07 and E08 are for specifying maximum and minimum value to output. These 2 values can be either positive or negative, however, E07 has to be smaller than E08.

  4. Use E09 to set output current milliamps when output data is out of the E07 and E08 range, there are 3 options:

    1. "2.4 & 21.6" stands for outputting 2.4mA when data is less than E07 value, and outputting 21.6mA when data is greater than E08 value.

    2. "2.4" stands for outputting 2.4mA when data is less than E07 value and greater than E08 value.

    3. "21.6" stands for outputting 2.4mA when data is less than E07 value and greater than E08 value.

  5. Turn on F02.

  6. Please enter the E11 parameter page to test and adjust 4mA output current. Adjustment unit is uA.

  7. Please enter the E12 parameter page to test and adjust 20mA output current. Adjustment unit is uA..

  8. If the output current is too low and can not reach 20mA after adjustment, please check the for line impedance and supply voltage requirement.

  9. Turn off F02 and go back to the monitoring screen.

  10. Finish.

parameter set-up page.
electrical installation page
mechanical and electrical installation.
mechanical and electrical installation.