Read-write memory list
Register location
Register length
Memory definition
Data type
Read-write function
Remarks
A group parameters
0000
1
pipe type
unsigned int 16
R/W
Multiple choice parameter type
0001
2
scale factor
float 32
R/W
0003
1
anti noise
unsigned int 16
R/W
Multiple choice parameter type
0004
1
damping
unsigned int 16
R/W
0005
1
direction
unsigned int 16
R/W
Multiple choice parameter type
0006
1
neg flow
unsigned int 16
R/W
Multiple choice parameter type
0007
1
ext mode
unsigned int 16
R/W
Multiple choice parameter type
B group parameters
0100
1
vol unit
unsigned int 16
R/W
Multiple choice parameter type
0101
1
time unit
unsigned int 16
R/W
Multiple choice parameter type
0102
1
total unit
unsigned int 16
R/W
Multiple choice parameter type
0103
1
speed unit
unsigned int 16
R/W
Multiple choice parameter type
C group parameters
0200
1
total method
unsigned int 16
R/W
Multiple choice parameter type
0201
1
clear total
unsigned int 16
W
0202
1
history function
unsigned int 16
R/W
Multiple choice parameter type
0203
1
clear history
unsigned int 16
W
D group parameters
0300
1
paddle alarm
unsigned int 16
R/W
Multiple choice parameter type
0301
1
magnetic alarm
unsigned int 16
R/W
Multiple choice parameter type
0302
1
battery alarm
unsigned int 16
R/W
Multiple choice parameter type
0303
1
flow limit alarm
unsigned int 16
R/W
Multiple choice parameter type
0304
2
upper limit
float 32
R/W
0306
2
lower limit
float 32
R/W
0308
1
hyster value
unsigned int 16
R/W
0309
1
total alram
unsigned int 16
R/W
Multiple choice parameter type
030A
1
total trigger
unsigned int 16
R/W
Multiple choice parameter type
030B
2
total target
float 32
R/W
030D
1
iout alarm
unsigned int 16
R/W
Multiple choice parameter type
030E
1
velocity alarm
unsigned int 16
R/W
Multiple choice parameter type
030F
1
slow pulse alarm
unsigned int 16
R/W
Multiple choice parameter type
E group parameters
0400
1
nc no
unsigned int 16
R/W
Multiple choice parameter type
0401
1
oct info
unsigned int 16
R/W
Multiple choice parameter type
0402
1
pulse width
unsigned int 16
R/W
Multiple choice parameter type
0403
1
modbus address
unsigned int 16
R/W
0404
1
modbus baud
unsigned int 16
R/W
Multiple choice parameter type
0405
1
iout definition
unsigned int 16
R/W
Multiple choice parameter type
0406
2
4mA value
float 32
R/W
0408
2
20mA value
float 32
R/W
040A
1
iout error
unsigned int 16
R/W
Multiple choice parameter type
040B
2
4mA adj
float 32
R/W
040D
2
20mA adj
float 32
R/W
F group parameters
0500
2
sim rate
float 32
R/W
0502
1
sim on - reserved
const
R
0503
1
sim pulse - reserved
const
R
G group parameters
0600
1
set year*1
unsigned int 16
R/W
0601
1
set month*1
unsigned int 16
R/W
0602
1
set day*1
unsigned int 16
R/W
0603
1
set time*2
unsigned int 16
R/W
0604
1
date format
unsigned int 16
R/W
Multiple choice parameter type
H group parameters
0700
1
led brightness
unsigned int 16
R/W
Multiple choice parameter type
0701
1
lcd brightness
unsigned int 16
R/W
Multiple choice parameter type
0702
1
green light
unsigned int 16
R/W
Multiple choice parameter type
0703
1
lang
unsigned int 16
R/W
0704
1
paddle init
unsigned int 16
W
0705
1
reset
unsigned int 16
W
Each definition of multiple choice memory type
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0000
pipe type
0
1 inch PVC T-connector
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0003
anti noise
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0005
direction
0
normal
1
inverse
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0006
neg flow
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0007
ext mode
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0100
vol unit
0
L
1
m3
2
us gal
3
imp gal
4
ft3
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0101
time unit
0
second
1
minute
2
hour
3
day
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0102
total unit
0
L
1
m3
2
us gal
3
imp gal
4
ft3
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0103
speed unit
0
m/s
1
ft/s
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0200
total method
0
pos
1
neg
2
net
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0202
history function
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0300
paddle alarm
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0301
magnetic alarm
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0302
battery alarm
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0303
flow limit alarm
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0309
total alarm
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
030A
total trigger
0
higher than target
1
lower than target
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
030D
iout alarm
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
030E
velocity alarm
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
030F
slow pulse alarm
0
off
1
on
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0400
nc no
0
nc
1
no
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0401
oct info
0
alarm a
1
alarm a b
2
alarm a b c
3
over flow volume
4
over total
5
paddle pulse
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0402
pulse width
0
0.5ms
1
1ms
2
10ms
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0404
modbus baud
0
9600
1
19200
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0405
iout definition
0
flow volume
1
velocity
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
040A
iout error
0
2.4 mA & 21.6 mA
1
2.4 mA
2
21.6 mA
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0604
date format
0
yyyy-mm-dd
1
yyyy/mm/dd
2
dd/mm/yyyy
3
mm/dd yy
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0700
led brightness
0
low
1
medium
2
high
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0701
lcd brightness
0
low
1
medium
2
high
Memory address
Memory definition
unsigned int 16 value
Corresponding option
Remarks
0702
green light
0
always on
1
10 seconds
2
60 seconds
Last updated