FP-AS510 Paddle Wheel Flowmeter Instruction Manual
  • ⚠Safety instructions
  • This instruction manual version is v1.0
  • Measure principle and usage scenario
  • Warranty
  • Exterior, Spec, Model
    • Device
    • Paddle set
    • T-connector
  • Install and set-up
    • Mechanism installation
    • Mechanical and electrical installation
    • Parameter setup
  • Human machine interface
    • Introduction of human machine interface
    • Monitoring screen
    • Data interpretation on monitoring screens
    • Setup screen
  • Communication
    • OCT output
    • 4-20mA
    • RS485
    • Modbus RTU Protocol
      • Read-only memory read instruction(04) and memory lists
      • Read-write memory list
      • Read-write memory read instruction(03)
      • Read-write memory single Register write instruction(06)
      • Read-write memory double Register write instruction(30)
  • Parameters Table
  • Alarm and description of system conditions
  • Trouble and abnormality shooting
  • Certification
  • FP-AS510 Product Page
  • LORRIC English Website
  • LORRIC Integration and Application Center
Powered by GitBook
On this page
  • SPEC
  • Cable wiring
  • Parameter setup

Was this helpful?

Export as PDF
  1. Communication

RS485

Previous4-20mANextModbus RTU Protocol

Last updated 4 years ago

Was this helpful?

SPEC

Please see the page of

Cable wiring

Please see the page of

Parameter setup

Please refer to .

Set-up steps as below:

  1. Connect cable according to the cable wiring section on this page.

  2. This machine uses Modbus RTU protocol, communication parameter set-up as below.:

    1. Set E04 for RS485 address, and please make sure there is no other device using the same address.

    2. Set E05 for specifying communication Baud, this machine supports 9600, 19200, 38400 and 57600.

  3. Please go back to the monitoring screen. RS485 only responses on monitoring screens.

  4. If needed, please use F01 and F02 to set up the machine to do communication test under simulation mode.

  5. Please refer to the for testing the memory with read and write instruction.

  6. Turn off F02 simulation mode.

  7. Finish.

parameter set-up page
Modbus RTU protocol page
mechanical and electrical installation.
mechanical and electrical installation.