Read-write memory single Register write instruction(06)
This instruction if for memory with 1 register length only, please refer to the list.
Instruction example
Format of command (06) from master
Description of master command
This example will change A01 pipe diameter option
slave address: 01(address of this flowmeter)
function code: 06(Single Register write instruction)
Address of first reading register: 0000(memory address to write)
Write data: 0000 (1" PVC pipe)
CRC: C40B (Calculating error correcting code according to CRC algorithm)
Format of flowmeter response(06)
Description of flowmeter response example
Valid command received. It will output the same command back to master.
slave address: 01(address of this flowmeter)
function code: 06(Single Register write instruction)
Address of first reading register: 0000(memory address to write)
Write data: 0000 (1" PVC pipe)
CRC: C40B (Calculating error correcting code according to CRC algorithm)
Last updated