F Category Options and Descriptions
F01 Sim. Rate (Simulation Rate)
Defines the instantaneous flow rate to simulate. The unit applied will follow the settings defined in the B classification parameters. Default Value 60.
Default
60
Minimum
0
Maximum
100000
F02 Sim. Mode (Simulation Mode)
Activating this option enables the simulation function, which is disabled by default. When enabled, the NPN outputs (excluding pulse), RS485 communication, and analogue current output will operate based on the simulated data and changes in the totalised flow. Default Value 0.
Please note that the totalised flow and historical data will be affected.
The main screen will display an indication that the system is in simulation mode. Ensure the relevant communication functions are enabled for proper operation.
OFF
0
Default
ON
1
After selecting a command, confirm whether to Save or Not Save.
F03 Sim. PulseHz (Simulation PulseHz)
Under this page, pulse signal will be outputted according to set frequency within value 0 to 1000. Please set up NC/NO of pulse according to parameter E01, and pulse width according to parameter E03. Default Value 10. It operates whether NPN info is turned on or not.
Default
10
Minimum
1
Maximum
1000