Parameter Configuration

  1. Set pipeline model – Parameter A01

  2. Set volume unit – Parameter B01

  3. Set time unit – Parameter B02

  4. Set totalised flow unit – Parameter B03

  5. Return to the main screen and verify the flow direction. If needed, configure flow direction settings via Parameters A05 and A06.

  6. Return to the main screen again to ensure data readings appear normal, or make fine adjustments using Parameter A02.

  7. If communication settings are required, proceed to configure parameters under Category E (Communication Settings).

  8. It is recommended to use the simulation test parametersF01, F02, F03 – to verify communication with the control system.

  9. Remove the main unit and check if Alarm A is triggered after 1 second. Reinstall the unit; the LCD should return to green.

  10. Finally, set the main display screen to show one of the following:

  • Instantaneous flow rate

  • Instantaneous flow velocity

  • Totalised flow volume

  1. Setup complete.It is recommended to refer to the complete parameter reference page for detailed firmware configuration guidance.

It is recommended to refer to the complete parameter reference page for detailed firmware configuration guidance. the page for a complete parameter description of the firmware set

Last updated