Under normal conditions(when the oct condition does not meet). NPN should be closely (connected) or open (disconnected). The default is open. (Applicable to Model FP-AS310A)
Options
RS-485 Numbers
Remarks
Normal Close
0
Default
Normal Open
1
After selecting a command, confirm whether to Save or Not Save.。
E02 Output Control Terminal Definition
There are options below are options to define NPN output:
OFF, Alarm A, Alarm A+B, Alarm A+B+C, flow volume alarm(adjusted by D04 D05 D06),
cumulation alarm(adjusted by D08 D09 D10), paddle wheel PulseV2 output( adjusted by E03, please refer to the OCT output for instructions).
Default OFF (Applicable to Model FP-AS310A)
Options
RS-485 Numbers
Remarks
Alarm b
1
Pulse 2.0
5
Off
6
Default
After selecting a command, confirm whether to Save or Not Save.
E03 Pulse Width
Defines the pulse width when E02 is set to PulseV2.
Selectable values: 1ms, 10ms, 50ms, 100ms。 Default: 1 ms. (Applicable to Model FP-AS310A)
Options
RS-485 Numbers
Remarks
1 ms
1
Default
10 ms
2
50 ms
3
100 ms
4
After selecting a command, confirm whether to Save or Not Save.
E04 Modbus ID
Configures the transmission protocol for Modbus ID. Default: 1.(Applicable to Model FP-AS310R)
Parameter Input Range
Values
Data Type
Int
Default
1
Minimum
1
Maximum
255
E05 Baud
Defines the Modbus communication baud rate. Options: 9600, 19200, 38400.
Default: Disabled. (Applicable to Model FP-AS310R)
Options
RS-485 Numbers
Remarks
9600
0
19200
1
38400
2
OFF
4
Default
The baud rate cannot be modified via RS485.
After selecting a command, confirm whether to Save or Not Save.
E06 Iout Definition
Defines the data output via analogue signal. Options: Off, Flow, Velocity, or Cumulative Flow. The unit corresponds to settings in the B category. Default: Off. (Applicable to Model FP-AS310A)
Options
RS-485 Numbers
Remarks
Flowrate
0
OFF
3
Default
After selecting a command, confirm whether to Save or Not Save.
E07 4mA Value
Sets the value corresponding to 4mA.
Positive and negative values are accepted, but this value must be less than the 20mA Value. Default: 0 (Applicable to Model FP-AS310A)
Parameter Input Range
Values
Default
0
Minimum
-100000
Maximum
100000
E08 20mA Value
Sets the value corresponding to 20 mA. Positive and negative values are accepted, but this value must be greater than the 4mA Value. Default: 100. (Applicable to Model FP-AS310A)
Parameter Input Range
Values
Default
100
Minimum
-100000
Maximum
100000
E11 4mA Output Adjustment in microAmp
Allows fine-tuning of the 4mA output value, in units of microamps (uA). Adjustments immediately affect output current for real-time verification. (Applicable to Model FP-AS310A)
Positive values increase the output. Negative values decrease the output.
Parameter Input Range
Values
Default
0
Minimum
-2000
Maximum
2000
E12 20mA Output Adjustment in microAmp
Allows fine-tuning of the 20 mA output value, in units of microamps (uA). Adjustments immediately affect output current for real-time verification. (Applicable to Model FP-AS310A)
Positive values increase the output. Negative values decrease the output.
Parameter Input Range
Values
Default
0
Minimum
-2000
Maximum
2000
E14 PulseV2 Unit
Define how much flow volume to output a pulse, the unit is determined by B01.
Default 0.001 ms. (Applicable to Model FP-AS310A)
Options
RS-485 Numbers
Remarks
0.001 unit
0
Default
0.002 unit
1
0.003 unit
2
0.005 unit
3
0.007 unit
4
0.01 unit
5
0.02 unit
6
0.03 unit
7
0.05 unit
8
0.07 unit
9
0.1 unit
10
0.2 unit
11
0.3 unit
12
0.5 unit
13
0.7 unit
14
1 unit
15
After selecting a command, confirm whether to Save or Not Save.