FP-AS510 Paddle Wheel Flowmeter Instruction Manual
LORRIC.com
  • ⚠Safety instructions
  • This instruction manual version is v2.0
  • Measure principle and usage scenario
  • Warranty
  • Exterior, Spec, Model
    • Device
    • Paddle set
    • T-connector
  • Install and set-up
    • Mechanism installation
    • Mechanical and electrical installation
    • Parameter setup
  • Human machine interface
    • Introduction of human machine interface
    • Monitoring screen
    • Simulation Mode
    • Data interpretation on monitoring screens
    • Password input page
    • Setup screen
  • Communication
    • OCT output
    • Analog current output (0-20mA, 4-20mA)
    • RS485 and Modbus RTU Setting
    • Modbus RTU Protocol
      • Read-only memory read instruction(04) and memory lists
      • Read-write memory list
      • Read-write memory read instruction(03)
      • Read-write memory single Register write instruction(06)
      • Read-write memory double Register write instruction(30)
  • Parameters Table
  • Alarm and description of system conditions
  • Trouble and abnormality shooting
    • Iout 4-20/0-20mA debug process
    • RS485 Debug Process
  • Certification
  • FP-AS510 Product Page
  • LORRIC English Website
  • LORRIC Integration and Application Center
Powered by GitBook
On this page
Export as PDF
  1. Trouble and abnormality shooting

Iout 4-20/0-20mA debug process

PreviousTrouble and abnormality shootingNextRS485 Debug Process

Last updated 4 years ago

Environment and parameter check

  1. To confirm if the power supply works fine.

  2. To confirm if the data on the LED screen is transferred to the system.

  3. To confirm if the Iout function is still on.

  4. To confirm if the low point value is 0 or 4mA.

  5. To confirm the setting of the corresponding value range.

  6. To confirm if wire wiring is correct and the insulation of unused wires is finished.

Hardware, wiring, and program of the receiver check

  1. If the wiring during the above test is different from the actual operation, please re-test.

Exporting of the device check

  1. Separating the Iout wiring from the system, then using the multimeter MA stalls to confirm if the current export works fine.

Results and actions

  1. If the data is still abnormal when both the Iout export function and the equipment and program of receiver work fine, some other possible reason, like pipe size, or paddle wheel abnormal, should be checked further.

  2. The current device may be damaged possibly. If users have another device for cross test, please make sure receiving equipment, data processing program, or wiring work fine.

  3. Contact the original manufacturer with the serial number, wiring diagram (all related wiring of the flowmeter), and the model and brand of receiver.

  4. Make sure if receiving equipment, data processing program, or wiring work fine.

Users need to refer to the actual situation, detailed troubleshooting, please contact LORRIC.

To get into to check if the 4/0mA export and interpretation function of the receiver (If there is a difference between data to data, users could adjust it by the unit uA at this page) works fine.

To get into to check if the 20mA export and interpretation function of the receiver works fine. (If there is a difference between data to data, users could adjust it by the unit uA at this page.)

To confirm if the interpretation function of the receiver works fine under simulation mode when testing different data. Simulation mode must be switched off when testing is finished. (Users can switch on the simulation mode by too, and adjust the simulated data by . Back to the main page while finishing data adjustment.)

(Parameter E06)
(Parameter E13)
(Parameter E07 E08)
parameter E11
parameter E12
parameter F02
parameter F01