FP-AS510 Paddle Wheel Flowmeter Instruction Manual
LORRIC.com
  • ⚠Safety instructions
  • This instruction manual version is v2.0
  • Measure principle and usage scenario
  • Warranty
  • Exterior, Spec, Model
    • Device
    • Paddle set
    • T-connector
  • Install and set-up
    • Mechanism installation
    • Mechanical and electrical installation
    • Parameter setup
  • Human machine interface
    • Introduction of human machine interface
    • Monitoring screen
    • Simulation Mode
    • Data interpretation on monitoring screens
    • Password input page
    • Setup screen
  • Communication
    • OCT output
    • Analog current output (0-20mA, 4-20mA)
    • RS485 and Modbus RTU Setting
    • Modbus RTU Protocol
      • Read-only memory read instruction(04) and memory lists
      • Read-write memory list
      • Read-write memory read instruction(03)
      • Read-write memory single Register write instruction(06)
      • Read-write memory double Register write instruction(30)
  • Parameters Table
  • Alarm and description of system conditions
  • Trouble and abnormality shooting
    • Iout 4-20/0-20mA debug process
    • RS485 Debug Process
  • Certification
  • FP-AS510 Product Page
  • LORRIC English Website
  • LORRIC Integration and Application Center
Powered by GitBook
On this page
  • Instantaneous flow volume and deviation
  • Flow speed
  • Cumulative flow speed and historical data.
Export as PDF
  1. Human machine interface

Data interpretation on monitoring screens

PreviousSimulation ModeNextPassword input page

Last updated 5 years ago

Instantaneous flow volume and deviation

The maximum possible deviation for LORRIC’s paddle wheel flow meter is 0.5 % F.S. + 2.5 % O.R. which could be converted to the relation of maximum possible deviation and displayed data under different flow speed as seen below.

Flow speed

The data displayed on the screen is the flow speed in the T-connector. In most cases it will be a bit faster than the flow speed of same ordinary pipe at the same flow volume.

Cumulative flow speed and historical data.

Flow volume will be accumulated continuously until it is manually zeroed.

Maximum cumulative flow volume is 999,999,999 Litre and will be zeroed until it is exceeded.

Calculation of historical flow volume is based on the following rules.

  1. If cumulative flow volume is not zeroed on a certain day (ex. 2020/01/01), then the data on that day is the data at 23:59:59 minus the data at 23:59:59 on the previous day.

  2. If cumulative flow volume is zeroed on a certain day, then data on that day is the data by 23:59:59.

Date data of historical flow volume is based on the following rules.

  1. Recorded data will not be changed. Therefore, artificially setting a data recording date earlier than the previous one makes recorded data being the same or earlier between new and previous date.

Parameter affects historical data and flow direction. Historical date data is set by classification ​

​

C1
G of the parameter.