FP-AS510 Paddle Wheel Flowmeter Instruction Manual
LORRIC.com
  • ⚠Safety instructions
  • This instruction manual version is v2.0
  • Measure principle and usage scenario
  • Warranty
  • Exterior, Spec, Model
    • Device
    • Paddle set
    • T-connector
  • Install and set-up
    • Mechanism installation
    • Mechanical and electrical installation
    • Parameter setup
  • Human machine interface
    • Introduction of human machine interface
    • Monitoring screen
    • Simulation Mode
    • Data interpretation on monitoring screens
    • Password input page
    • Setup screen
  • Communication
    • OCT output
    • Analog current output (0-20mA, 4-20mA)
    • RS485 and Modbus RTU Setting
    • Modbus RTU Protocol
      • Read-only memory read instruction(04) and memory lists
      • Read-write memory list
      • Read-write memory read instruction(03)
      • Read-write memory single Register write instruction(06)
      • Read-write memory double Register write instruction(30)
  • Parameters Table
  • Alarm and description of system conditions
  • Trouble and abnormality shooting
    • Iout 4-20/0-20mA debug process
    • RS485 Debug Process
  • Certification
  • FP-AS510 Product Page
  • LORRIC English Website
  • LORRIC Integration and Application Center
Powered by GitBook
On this page
Export as PDF
  1. Install and set-up

Parameter setup

PreviousMechanical and electrical installationNextHuman machine interface

Last updated 4 years ago

Recommend flow of parameter set-up

  1. Set A1 for the Pipe type

  2. Set B1 for the flow rate volume unit

  3. Set B2 for the flow volume time unit

  4. Set B3 for the cumulative volume unit

  5. Press ESC several times, Go back to monitor screen, check if flow direction is expected, use A04 A05 to change flow direction display

  6. In the monitor screen, check if the flow volume is as expected, use A02 to scale flow volume.

  7. E type parameters are for communication setup

  8. F type parameter for communication simulation

  9. Remove the device from the T-connector, and check if the lcd backlight blinks a red light. Reinstall the device and check if the LCD monitor goes back to a green light.

  10. Leave the device screen on one of 3 monitoring screens (flow volume, flow speed, totalizer).

  11. Finish.

Refer to

the page for a complete parameter description of the firmware set-up.