OCT output

Specifications

NPN, PNP Output

Power Supply

5-30V 200mA

Reverse Polarity Protection

Yes

Wiring

NPN, PNP

Current Consumption

200 mA @ 12V during stable operation at startup (excluding communication current)

Wiring

OCT NPN Output Wiring Diagram

  • Brown: 24 VDC (+), Blue: 0 VDC (–), Orange: OCT Output (+), Yellow: OCT Output (−)

The OCT output circuit operates with a loop power of 5–30 VDC, 200 mA. This function requires the brown and blue lines of the main DC power supply to be powered. For clarity, the DC power lines are omitted from this diagram. Refer to the DC Power Wiring Diagram for details.

OCT PNP Output Wiring Diagram

Brown: 24 VDC (+), Blue: 0 VDC (−), Orange: OCT Output (+), Yellow: OCT Output (−)

The OCT output circuit operates with a loop power of 5–30 VDC, 200 mA. This function requires the brown and blue lines of the main DC power supply to be powered. For clarity, the DC power lines are omitted from this diagram. Refer to the DC Power Wiring Diagram for details.

OCT Parameter Configuration

Follow the steps below to configure OCT output parameters:

1

Set Basic Parameters

2

Wiring Setup

Connect the OCT output wiring according to the instructions on this page.

3

E01 NC/NO (Normally Closed or Normally Open)

Set parameter E01 NC/NO to select the default state when there is no signal:

  • NC (Normally Closed): Conducting when idle

  • NO (Normally Open): Open when idle

4

E02 OCT Definition (Output Signal Type)

Set parameter E02 OCT Info to specify the output signal type.

  • If "Pulse Output" is selected:

    1. Use E03 Pulse Width to set the duration of each pulse.

    2. Use F03 to simulate the pulse output and verify that the receiving end correctly receives the pulse count.

  • If "Pulse V2" is selected:

    1. Use E03 Pulse Width to set the duration of each pulse.

    2. Use E14 Pulse V2 Unit to define the volume represented by each pulse.

    3. Use F03 to simulate the pulse output and verify that the receiving end correctly receives the pulse count.

  • If "Total Alarm" is selected:

    1. Use D08 Total Alarm to enable the alarm.

    2. Use D09 Total Trig. to set the trigger condition:

      • "Greater than Target" for forward flow

      • "Less than Target" for reverse flow

    3. Use D10 Total Target to specify the cumulative target:

      • Positive value for forward flow

      • Negative value for reverse flow

    (See Note 1)

  • If "Flow Alarm" is selected:

    1. Use D04 FlowLIM Alarm to enable the flow range alarm.

    2. Use D05 UP LIM (Upper Limit) and D06 Low LIM (Lower Limit) to define the normal flow range.

      Note: If either D05 or D06 is adjusted, the other must also be set; otherwise the display may not function correctly. If both are unset, default values are D05 = 100, D06 = 0.

    3. Use D07 Hysteresis to define the hysteresis operation method. Values must be positive and expressed as a percentage; larger values reduce repeated alarm triggers.

    (See Note 2)

5

Return to the Main Screen. Complete.

Note 1

Note 2

Pulse output

Pulse output is based on the frequency of the paddle wheel’s revolutions. A pulse will be sent by every 180° revolution. At a flow rate of 10m/s, the maximum frequency will not exceed 300 Hz. Since the data processing technology of LORRIC is not used, it is recommended to use it in an environment with lower accuracy requirements. To calculate the total flow volumes for a certain period of time, count the number of pulse signals received then divided by the corresponding proportion this manual provides. Proportion is defined by pipe size and material. Please refer to the following information.

Plastic (PVC, PP, PVDF) T-connector

Pipe diameter

Model

Metric ratio (pulses per litre)

US Gallon (pulses per US gal)

UK Gallon (pulses per UK gal)

1/2"

FP-P016

106.55

403.33

484.38

3/4"

FP-P020

67.23

254.48

305.62

1"

FP-P025

53.33

201.89

242.46

1-1/4"

FP-P032

24.44

92.51

111.11

1-1/2"

FP-P040

17.02

64.43

77.38

2"

FP-P050

9.86

37.31

44.81

2-1/2"

FP-P065

5.42

20.52

24.64

PulseV2

This function has been tested in limited scenarios, it is still in the public testing stage. Please test and carefully evaluate the applicability before using it

PulseV2 is an exclusive function developed by LORRIC based on patented AxelSense technology. The unique algorithm allows the users to select a fixed volume, and the device will output a pulse every time a unit volume flows. The device can also intelligently correct error at low flow rate, making smaller pulse data error. Compared with the traditional pulse output, which directly outputs the revolutions of paddle wheel, every time the blade sweeps over the Sensor and outputs a pulse. “PulseV2” has two advantages: 1. The user can easily understand how to set up the controller. 2. Error of low flow rate is smaller.