A10 Liquid Type

Definition

Set the liquid type. Default: custom.

Notes

N/A

Operation Procedure

Button Functions (Click to Expand)

When the main screen is displayed in green backlight, the four buttons function as follows:

  • Blue Button (leftmost): Return, exit, or save settings.

  • Gray Direction Buttons:

    • Left Gray: Previous Page, decrease value, or select item

    • Right Gray: Next Page, increase value, or select item

  • Orange Button (rightmost): Rightmost button: Enter settings, edit, or confirm selection

Button functions may change depending on the operation context to improve usability or prevent accidental presses.

A10 Liquid Type Setting Steps
• From the main screen (green backlight), 
press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select A. Measurement , press Orange Button (Enter).
• Use Gray Arrow Buttons to select A10 Liquid Type, press Orange Button (Enter).
• Use Gray Arrow Buttons to choose the options. 
• Press Orange Button (Set) to confirm.
• Press Blue Button (ESC) to return to the main screen (green backlight).

A10 Options, RS485 Values, Read/Write Commands, and Formats

Option
Description
RS-485 Value

Custom (Custom)

Custom

0

Water 20℃

68°F

1

Water 50℃

122°F

2

Water 75℃

167°F

3

Water 100℃

212°F

4

Water 125℃

257°F

5

Water 150℃

302°F

6

Water 175℃

347°F

7

Water 200℃

392°F

8

Water 225℃

437°F

9

Acetone

10

Carbinol

11

Ethanol

12

Alcohol

13

Acetaldehyde

14

Arachis Oil

15

Glycerin

16

Gasoline

17

Benzene

18

Ethyl Benzene

19

Toluene

20

4-Chloromethane

21

Petroleum

22

Pine Oil

23

Cloroethylene

24

Ketone

25

Glycol

26

Sea Water

27

Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the Int16 data format.

Last updated