Definition

Set the pipe inner diameter. Default values vary depending on the selected pipe unit.

Inner Diameter
Default
Minimum
Maximum

DN15

16.6 mm

0.654 inch

5 mm

0.197 inch

29 mm

1.142 inch

DN20

20.9 mm

0.811 inch

7 mm

0.276 inch

33.4 mm 1.315 inch

DN25

25.6 mm

.008 inch

12 mm

0.472 inch

41 mm

1.614 inch

DN32

31.6 mm

1.244 inch

18 mm

0.709 inch

51 mm

2.008 inch

DN40

40.6 mm

1.598 inch

23 mm

0.906 inch

63 mm

2.48 inch

DN50

51.8 mm

2.039 inch

30 mm

1.181 inch

76 mm

2.992 inch

DN65

67.8 mm

2.669 inch

38 mm

1.496 inch

89.2 mm

3.512 inch

DN75

78.2 mm

3.079 inch

46 mm

1.811 inch

117 mm

4.606 inch

DN100

100.8 mm

3.969 inch

88.9 mm

3.5 inch

102.3 mm

4.028 inch

DN125

126 mm

4.961 inch

114.6 mm

4.512 inch

128.2 mm

5.047 inch

DN150

146 mm

5.748 inch

130.8 mm

5.15 inch

154.06 mm

6.065 inch

DN200

194.4 mm

7.654 inch

182.6 mm

7.189 inch

203.4 mm

8.008 inch

DN250

240.4 mm

9.465 inch

229.2 mm

9.024 inch

254.51 mm

10.02 inch

DN300

286.2 mm

11.268 inch

257.8 mm

10.15 inch

303.23 mm

11.938 inch

DN350

332 mm

13.071 inch

290.6 mm

11.441 inch

349 mm

13.74 inch

DN400

376 mm

14.803 inch

327.4 mm

12.89 inch

396.4 mm

15.606 inch

Notes

  1. Pipe size units are determined by B06 (Pipe Size Unit).

  2. Each time the pipe size is changed, please re-execute Z03 Auto Initialize and Z04 Auto Zero Offset to improve measurement accuracy and ensure stable product performance.

  3. On certain firmware versions, a pipe material confirmation page will appear after setting A07 Pipe Wall Thickness. Please select the matching pipe material or choose Custom. If a predefined pipe material is selected, A08 (Pipe Material) will be synchronized automatically.

  4. For DN100–DN400, Default corresponds to A02's CNS W specification; Minimum/Maximum are the smallest and largest inner diameter among all specifications listed in A02 (Preset Pipe Spec) for that size.

Operation Procedure

Button Functions (Click to Expand)

When the main screen is displayed in green backlight, the four buttons function as follows:

  • Blue Button (leftmost): Return, exit, or save settings.

  • Gray Direction Buttons:

    • Left Gray: Previous Page, decrease value, or select item

    • Right Gray: Next Page, increase value, or select item

  • Orange Button (rightmost): Rightmost button: Enter settings, edit, or confirm selection

Button functions may change depending on the operation context to improve usability or prevent accidental presses.

A07 Options, RS485 Values, Read/Write Commands, and Formats

Refer to the table above
Refer to the table above
Refer to the table above

Custom

Refer to the table above

-

Minimum

-

Maximum

-

Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the float 32 data format.

Last updated