E15 Byte Format
Definition
Sets the data format for Modbus RTU communication. Default: N,8,1 (No parity, 8 data bits, 1 stop bit).
This parameter offers four byte packet formats:
N.8.1
No parity bit with 1 stop bit
N.8.2
No parity bit with 2 stop bits
O.8.1
Odd parity bit with 1 stop bit.
E.8.1
Even parity bit with 1 stop bit
The diagram below illustrates each packet format. ST represents the start bit, D0–D7 are data bits, SP is the stop bit, OP indicates odd parity, and EP indicates even parity. (Each diamond shape represents one bit.)

Modbus Formats Converter
Notes
This parameter cannot be modified via RS485.
For details, refer to the RS485 and Modbus RTU Settings section.
Operation Procedure
Button Functions (Click to Expand)
The main unit has four buttons. The bottom line (Line 3) of the LCD displays the current function of each button. Under normal operation, the button functions are as follows:
Blue Button - Leftmost button: Return, exit, or save settings.
Gray Arrow Buttons:
Left Gray Button: Page up, increase value, or select item
Right Gray Button: Page down, decrease value, or select item
Orange Button: Rightmost button: Enter settings, edit, or confirm selection
Do not hold buttons for extended periods to avoid damage.
Button functions may change depending on the operation context to improve usability or prevent accidental presses.

E15 Options, RS485 Values, Read/Write Commands, and Formats
N.8.1 (Default)
No parity, 8 data bits, 1 stop bit
-
N.8.2
No parity, 8 data bits, 1 stop bit
-
O.8.1
Odd parity, 8 data bits, 1 stop bit
-
E.8.1
Even parity, 8 data bits, 1 stop bit
-
This parameter cannot be modified via RS485.