E08 20mA Value

Definition

Sets the value corresponding to 20 mA on the flow meter. Both positive and negative values are allowed. Default: 100.

Notes

The 20 mA value must be greater than the 4 mA value.

Operation Procedure

chevron-rightButton Functions (Click to Expand)hashtag

The main unit has four buttons. The bottom line (Line 3) of the LCD displays the current function of each button. Under normal operation, the button functions are as follows:

  • Blue Button - Leftmost button: Return, exit, or save settings.

Gray Arrow Buttons:

  • Left Gray Button: Page up, increase value, or select item

  • Right Gray Button: Page down, decrease value, or select item

  • Orange Button: Rightmost button: Enter settings, edit, or confirm selection

triangle-exclamation
circle-info

Button functions may change depending on the operation context to improve usability or prevent accidental presses.

E08 20mA Value Setting Steps
• From the main screen (green backlight), 
  press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select E. Commute , press Orange Button (Enter).
• Use Gray Arrow Buttons to select E08 20mA Value, press Orange Button (Enter).
• Use Gray Arrow Buttons to choose the options. 
• Press Orange Button (Set) to confirm.
• Press Blue Button (ESC) to return to the main screen (green backlight).

E08 Options, RS485 Values, Read/Write Commands, and Formats

Parameter Input Range
Corresponding Values
RS-485 Value

Default

100

-

Minimum

-100000

-

Maximum

100000

-

Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the float 32 data format.