For the complete documentation index, see llms.txt. This page is also available as Markdown.

D09 Total Alarm

Definition

Set the flow meter’s alarm mode for totalizer values exceeding the set range. Default: Off. The alarm code belongs to Alarm – B. (D09 , D10 , and D11 work together to enable totalizer target alarm functionality.)

D09、D10、D11 Total Alarm Examples
Example 1: Forward Flow
Enable D09 Total Alarm.
Set D10 Total Trig. to “Greater than Target”.
Set D11 Total Target to a positive value, e.g., +100.
When the cumulative forward flow exceeds 100, 
the system triggers the total alarm.

Example 2: Reverse Flow
Enable D09 Total Alarm.
Set D10 Total Trig. to “Less than Target”.
Set D11 Total Target to a negative value, e.g., -500.
When the cumulative reverse flow drops below -500, 
the system triggers the total alarm.

Notes

DND (Do Not Disturb) Mode

  • System detects abnormalities, but red backlight remains off.

  • Example: Alarm-A “4 Off Pipe” triggers no backlight.

  • Abnormalities still appear on the Abnormalities page.

  • RS485 connection still sends alarm signals.

  • OCT output continues to signal alarms if configured.

Operation Procedure

Button Functions (Click to Expand)

The main unit has four buttons. The bottom line (Line 3) of the LCD displays the current function of each button. Under normal operation, the button functions are as follows:

  • Blue Button - Leftmost button: Return, exit, or save settings.

Gray Arrow Buttons:

  • Left Gray Button: Previous Page, decrease value, or select item

  • Right Gray Button: Next Page, increase value, or select item

  • Orange Button: Rightmost button: Enter settings, edit, or confirm selection

Button functions may change depending on the operation context to improve usability or prevent accidental presses.

Totalized Flow Alarm Function (Click to Expand)

This function triggers an alarm when the totalized flow reaches a value greater than or less than the preset target.

Related parameters: D09 Total Alarm, D10 Total Trigger Condition (Total Trig.), and D11 Total Target.

1

D09 Enable Totalizer Alarm

2

D10 Set Total Trigger Condition

3

D11 Set Total Target Value

4

Totalizer Alarm Operation

When the totalizer alarm is enabled and the accumulated flow meets the trigger condition, the system triggers Alarm B. The alarm bits (Bit6, Bit7) are set to 1, indicating that the alarm is active.

The alarm behavior follows the mode set in D09:

  • ON: The receiving system receives the alarm signal, and the meter displays a red backlight alarm.

  • Do Not Disturb (DND): The receiving system still receives the alarm signal, but the meter does not display a red backlight alarm.

D09 Options, RS485 Values, Read/Write Commands, and Formats

Option
Description
RS-485 Value

Off (Default)

-

0

On

-

1

Do Not Disturb

Do Not Disturb

2

Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the Int16 data format.

Last updated