D08 Hysteresis

Definition

Set the hysteresis percentage for clearing flow upper and lower limit alarms. This ensures the alarm is only cleared when the flow stabilizes back within the set range. The percentage is defined relative to the span between the upper and lower limits. Default: 03 (3%).

(D05 , D06 , D07 , and D08 work together to enable the flow range over-limit alarm function.)

chevron-rightFlow Range Limit Alarm Example (Click to Expand)hashtag
D06 Upper Limit: 30 LPM
D07 Lower Limit: 10 LPM
D08 Hysteresis: 3% (default)

Calculations:
Range: 30 − 10 = 20 LPM
Hysteresis: 20 × 3% = 0.6 LPM

Alarm Behavior:
When flow exceeds the upper limit (30 LPM), the alarm is triggered.
The alarm will clear only when the flow drops below 29.4 LPM (30 − 0.6).
When flow falls below the lower limit (10 LPM), the alarm is triggered.
The alarm will clear only when the flow rises above 10.6 LPM (10 + 0.6).

Notes

This parameter must be a positive value.

Operation Procedure

chevron-rightButton Functions (Click to Expand)hashtag

The main unit has four buttons. The bottom line (Line 3) of the LCD displays the current function of each button. Under normal operation, the button functions are as follows:

  • Blue Button - Leftmost button: Return, exit, or save settings.

Gray Arrow Buttons:

  • Left Gray Button: Page up, increase value, or select item

  • Right Gray Button: Page down, decrease value, or select item

  • Orange Button: Rightmost button: Enter settings, edit, or confirm selection

triangle-exclamation
circle-info

Button functions may change depending on the operation context to improve usability or prevent accidental presses.

chevron-rightFlow Range Over-Limit Alarm Operation (Click to Expand)hashtag

When the flow range alarm is enabled and the flow reaches the alarm condition, Alarm B is triggered. Alarm bits (Bit0, Bit1) display 1 to indicate the alarm has been activated.

The system responds according to the alarm mode set in D05:

  • On: The receiving device receives the alarm signal, and the flow meter screen displays a red backlight warning.

  • Do Not Disturb (DND): The receiving device still receives the alarm signal, but the screen does not display the red backlight.

Set D05 to enable the flow range over-limit alarmD05 FlowLIM Alarm Setting Steps• From the main screen (green backlight), press Orange Button (Setup) to enter settings (orange backlight).• Use Gray Arrow Buttons to select D. Alarm & Info, press Orange Button (Enter).• Use Gray Arrow Buttons to select D05 FlowLIM Alarm, press Orange Button (Enter).• Use Gray Arrow Buttons to choose the options. • Press Orange Button (Set) to confirm.• Press Blue Button (ESC) to return to the main screen (green backlight).Set D06 to define the flow upper limitD06 Up LIM Setting Steps• From the main screen(green backlight), press Orange Button(Setup) to enter settings (orange backlight).• Use Gray Arrow Buttons to select D. Alarm & Info, press Orange Button(Enter).• Use Gray Arrow Buttons to select D06 Up LIM, press Orange Button(Enter).• Use Gray Arrow Buttons to choose the digit to adjust(highlighted in dark gray).• Press Orange Button(Edit) to enter adjustment mode.• Adjust digits: Left Gray Button to increase, Right Gray Button to decrease.• Press Orange Button(Set) to confirm each digit; repeat for other digits as needed.• After all digits are set, press Blue Button(Save).• Confirm by pressing Orange Button(Save) (or Blue Button(NOT) to cancel).• Press Blue Button(ESC) to return to the main screen(green backlight).Set D07 to define the flow lower limitPipe Thickness Setting Steps• From the main screen(green backlight), press Orange Button(Setup) to enter settings (orange backlight).• Use Gray Arrow Buttons to select A. Measurement, press Orange Button(Enter).• Use Gray Arrow Buttons to select A06 Pipe Thickness, press Orange Button(Enter).• Use Gray Arrow Buttons to choose the digit to adjust(highlighted in dark gray).• Press Orange Button(Edit) to enter adjustment mode.• Adjust digits: Left Gray Button to increase, Right Gray Button to decrease.• Press Orange Button(Set) to confirm each digit; repeat for other digits as needed.• After all digits are set, press Blue Button(Save).• Confirm by pressing Orange Button(Save) (or Blue Button(NOT) to cancel).• Press Blue Button(ESC) to return to the main screen(green backlight).Set D08 to define the flow hysteresisD08 Hysteresis Setting Steps• From the main screen (green backlight), press Orange Button (Setup) to enter settings (orange backlight).• Use Gray Arrow Buttons to select D. Alarm & Info , press Orange Button (Enter).• Use Gray Arrow Buttons to select D08 Hysteresis, press Orange Button (Enter).• Use the Gray Arrow Buttons to adjust the flow hysteresis percentage:• Press the Left Gray Buttons to increase the value• Press the Right Gray Buttons to decrease the value• Press Orange Button (Set) to confirm.• Press Blue Button (ESC) to return to the main screen (green backlight).Flow Range Over-Limit Alarm OperationWhen the flow range alarm is enabled and the flow reaches the alarm condition, Alarm B is triggered. Alarm bits (Bit0, Bit1) display 1 to indicate the alarm has been activated.The system responds according to the alarm mode set in D05:On: The receiving device receives the alarm signal, and the flow meter screen displays a red backlight warning.Do Not Disturb (DND): The receiving device still receives the alarm signal, but the screen does not display the red backlight.

D08 Options, RS485 Values, Read/Write Commands, and Formats

Parameter Input Range
Corresponding Values
RS-485 Value

Default

03

3%

Minimum

00

0%

Maximum

10

10%

Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the Int16 data format.