D08 Hysteresis
Definition
Set the hysteresis percentage for clearing flow upper and lower limit alarms. This ensures the alarm is only cleared when the flow stabilizes back within the set range. The percentage is defined relative to the span between the upper and lower limits. Default: 03 (3%).
(D05 , D06 , D07 , and D08 work together to enable the flow range over-limit alarm function.)
Notes
This parameter must be a positive value.
Operation Procedure
D08 Options, RS485 Values, Read/Write Commands, and Formats
Parameter Input Range
Corresponding Values
RS-485 Value
Default
03
3%
Minimum
00
0%
Maximum
10
10%
Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the Int16 data format.