Set the totalizer to reset automatically at a specified interval. Range: 1–3600 seconds. Default: 300.
Dosing Function (Click to Expand)
1. Flow Meter Dosing Function Description
The dosing function controls a valve based on the flow meter’s totalizer. When the accumulated volume reaches the preset target, the valve closes automatically. After the set buffer time, the totalizer resets to zero, preparing for the next dosing cycle.
This function enables dosing control directly through the flow meter without an external PLC, making it suitable for chemical dosing, liquid replenishment, and batching applications.
2. Parameter Configuration Table
Parameter Code
Function
Description
Recommended Setting
E02
OCT Definition
Sets the control output mode
Must be set to Dosing mode
C03
Dosing Mode
Enables the dosing function
Set to On
C04
Dosing Target
Sets the target volume per dosing cycle
Enter as required (unit: L)
C05
Dosing Reset Time
Sets the buffer time after the target is reached before reset
Set based on system response time (unit: s)
H09
Startup Screen
Sets the main display screen
Set to Dosing mode screen
D16
Dosing Alarm
Alarm indication when dosing is completed
Enable as required or set to Do Not Disturb
3. Dosing Operation
After the valve opens, fluid flow begins and the flow meter accumulates volume in real time. When the accumulated volume reaches the dosing target set in C04, the system closes the valve according to the OCT output logic defined in E02, completing the dosing cycle. A “Dosing Complete” alarm is then triggered based on the D16 setting.
The system then enters the reset delay defined in C05. Once the delay time elapses, the totalizer is automatically reset to zero and the system is ready for the next dosing cycle.
Due to response time delays in valve actuation and control signals, the actual dosing result may differ slightly from the set value. This deviation becomes more noticeable with smaller dosing volumes, higher flow rates, or longer distances between the valve, flow meter, and container.
For higher dosing accuracy, select an appropriate pipe size and piping layout. It is recommended to perform on-site testing and adjust the calibration (scaling) factor as needed before actual operation.
Notes
To use the C05 function, also configure C03, C04, E02, and H09 accordingly.
Operation Procedure
Button Functions (Click to Expand)
The main unit has four buttons. The bottom line (Line 3) of the LCD displays the current function of each button. Under normal operation, the button functions are as follows:
Blue Button - Leftmost button: Return, exit, or save settings.
Gray Arrow Buttons:
Left Gray Button: Page up, increase value, or select item
Right Gray Button: Page down, decrease value, or select item
Orange Button: Rightmost button: Enter settings, edit, or confirm selection
Do not hold buttons for extended periods to avoid damage.
Button functions may change depending on the operation context to improve usability or prevent accidental presses.
C05 Dosing Reset Setting Steps
• From the main screen(green backlight),
press Orange Button(Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select C. Total, press Orange Button(Enter).
• Use Gray Arrow Buttons to select C05 Dosing Reset press Orange Button(Enter).
• Use Gray Arrow Buttons to choose the digit to adjust(highlighted in dark gray).
• Press Orange Button(Edit) to enter adjustment mode.
• Adjust digits: Left Gray Button to increase, Right Gray Button to decrease.
• Press Orange Button(Set) to confirm each digit; repeat for other digits as needed.
• After all digits are set, press Blue Button(Save).
• Confirm by pressing Orange Button(Save) (or Blue Button(NOT) to cancel).
• Press Blue Button(ESC) to return to the main screen(green backlight).
Main Screen 4 – Dosing
The dosing status can be monitored on the main screen. The first line of the LCD shows the C05 Reset Time, which counts down from the user-set C05 value. When it reaches zero, the totalizer automatically restarts the accumulation.
C05 Options, RS485 Values, Read/Write Commands, and Formats
Parameter Input Range
Corresponding Values
RS-485 Value
Default
300
-
Minimum
1
-
Maximum
3600
-
Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the float 32 data format.