C05 Dosing Reset Time

Definition

Set the totalizer to reset automatically at a specified interval. Range: 1–3600 seconds. Default: 300.

chevron-rightDosing Function (Click to Expand)hashtag

1. Flow Meter Dosing Function Description

The dosing function controls a valve based on the flow meter’s totalizer. When the accumulated volume reaches the preset target, the valve closes automatically. After the set buffer time, the totalizer resets to zero, preparing for the next dosing cycle.

This function enables dosing control directly through the flow meter without an external PLC, making it suitable for chemical dosing, liquid replenishment, and batching applications.

2. Parameter Configuration Table

Parameter Code
Function
Description
Recommended Setting

E02

OCT Definition

Sets the control output mode

Must be set to Dosing mode

C03

Dosing Mode

Enables the dosing function

Set to On

C04

Dosing Target

Sets the target volume per dosing cycle

Enter as required (unit: L)

C05

Dosing Reset Time

Sets the buffer time after the target is reached before reset

Set based on system response time (unit: s)

H09

Startup Screen

Sets the main display screen

Set to Dosing mode screen

D16

Dosing Alarm

Alarm indication when dosing is completed

Enable as required or set to Do Not Disturb

3. Dosing Operation

After the valve opens, fluid flow begins and the flow meter accumulates volume in real time. When the accumulated volume reaches the dosing target set in C04, the system closes the valve according to the OCT output logic defined in E02, completing the dosing cycle. A “Dosing Complete” alarm is then triggered based on the D16 setting.

The system then enters the reset delay defined in C05. Once the delay time elapses, the totalizer is automatically reset to zero and the system is ready for the next dosing cycle.

circle-info

Due to response time delays in valve actuation and control signals, the actual dosing result may differ slightly from the set value. This deviation becomes more noticeable with smaller dosing volumes, higher flow rates, or longer distances between the valve, flow meter, and container.

For higher dosing accuracy, select an appropriate pipe size and piping layout. It is recommended to perform on-site testing and adjust the calibration (scaling) factor as needed before actual operation.

Notes

To use the C05 function, also configure C03, C04, E02, and H09 accordingly.

Operation Procedure

chevron-rightButton Functions (Click to Expand)hashtag

The main unit has four buttons. The bottom line (Line 3) of the LCD displays the current function of each button. Under normal operation, the button functions are as follows:

  • Blue Button - Leftmost button: Return, exit, or save settings.

Gray Arrow Buttons:

  • Left Gray Button: Page up, increase value, or select item

  • Right Gray Button: Page down, decrease value, or select item

  • Orange Button: Rightmost button: Enter settings, edit, or confirm selection

triangle-exclamation
circle-info

Button functions may change depending on the operation context to improve usability or prevent accidental presses.

C05 Dosing Reset Setting Steps
• From the main screen(green backlight), 
  press Orange Button(Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select C. Total, press Orange Button(Enter).
• Use Gray Arrow Buttons to select C05 Dosing Reset press Orange Button(Enter).
• Use Gray Arrow Buttons to choose the digit to adjust(highlighted in dark gray).
• Press Orange Button(Edit) to enter adjustment mode.
• Adjust digits: Left Gray Button to increase, Right Gray Button to decrease.
• Press Orange Button(Set) to confirm each digit; repeat for other digits as needed.
• After all digits are set, press Blue Button(Save).
• Confirm by pressing Orange Button(Save) (or Blue Button(NOT) to cancel).
• Press Blue Button(ESC) to return to the main screen(green backlight).

Main Screen 4 – Dosing

The dosing status can be monitored on the main screen. The first line of the LCD shows the C05 Reset Time, which counts down from the user-set C05 value. When it reaches zero, the totalizer automatically restarts the accumulation.

C05 Options, RS485 Values, Read/Write Commands, and Formats

Parameter Input Range
Corresponding Values
RS-485 Value

Default

300

-

Minimum

1

-

Maximum

3600

-

Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the float 32 data format.

Last updated