1. Flow Meter Dosing Function Description
The dosing function controls a valve based on the flow meter’s totalizer. When the accumulated volume reaches the preset target, the valve closes automatically. After the set buffer time, the totalizer resets to zero, preparing for the next dosing cycle.
This function enables dosing control directly through the flow meter without an external PLC, making it suitable for chemical dosing, liquid replenishment, and batching applications.
2. Parameter Configuration Table
Parameter Code
Function
Description
Recommended Setting
Sets the control output mode
Must be set to Dosing mode
Enables the dosing function
Sets the target volume per dosing cycle
Enter as required (unit: L)
Sets the buffer time after the target is reached before reset
Set based on system response time (unit: s)
Sets the main display screen
Set to Dosing mode screen
Alarm indication when dosing is completed
Enable as required or set to Do Not Disturb
3. Dosing Operation
After the valve opens, fluid flow begins and the flow meter accumulates volume in real time. When the accumulated volume reaches the dosing target set in C04, the system closes the valve according to the OCT output logic defined in E02, completing the dosing cycle. A “Dosing Complete” alarm is then triggered based on the D16 setting.
The system then enters the reset delay defined in C05. Once the delay time elapses, the totalizer is automatically reset to zero and the system is ready for the next dosing cycle.