A18 Low Flow Cutoff

Definition

This function forces the flowmeter to display flow values below a set threshold as 0. The default value is 0, which disables the function.

When A18 Low Flow Cutoff is disabled, small near-zero measurement fluctuations may be displayed, causing slight value variations when the system is stopped.

To display a stable zero flow when the system is stopped, enable A18 to force flow values below the threshold to zero, preventing zero drift and minor measurement disturbances.

Notes

  1. The default value is 0, which means the function is disabled and the flowmeter will display actual small flow values.

  2. The condition “below the set value” is evaluated using the absolute value of the flow rate. Regardless of forward or reverse flow, any value lower than the set threshold will be displayed as 0.

  3. A18 is a hard cutoff for both display and output. When the actual flow rate is lower than the A18 setting, the flowmeter will display 0 and no flow variation within this range will be output.

  4. If the application requires measurement of small flow fluctuations near zero, the measured flow value must be greater than the A18 setting. Otherwise, the flow will be treated as 0 and cannot be measured or recorded.

  5. Setting Recommendations

    • General process display / PLC false-trigger prevention: Set A18 close to the lower measurement limit of the flowmeter model to improve zero stability.

    • Low-flow detection / micro-flow research applications: It is recommended to disable A18 (A18 = 0) to preserve full measurement information near zero flow.

*Lower measurement limit

DN

DN8

DN10

DN15

DN20

DN25

Lower measurement limit

1 LPM

1 LPM

2.5 LPM

2.5 LPM

5 LPM

Operation Procedure

chevron-rightButton Functions (Click to Expand)hashtag

The main unit has four buttons. The bottom line (Line 3) of the LCD displays the current function of each button. Under normal operation, the button functions are as follows:

  • Blue Button - Leftmost button: Return, exit, or save settings.

Gray Arrow Buttons:

  • Left Gray Button: Page up, increase value, or select item

  • Right Gray Button: Page down, decrease value, or select item

  • Orange Button: Rightmost button: Enter settings, edit, or confirm selection

triangle-exclamation
circle-info

Button functions may change depending on the operation context to improve usability or prevent accidental presses.

A18 Options, RS485 Values, Read/Write Commands, and Formats

Input Range of This Parameter
Corresponding Values
RS-485 Value

Custom

0

-

Minumum

0

-

Maximum

150,000,000

-

Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the float 32 data format.

Last updated