# A08 Pipe Material

### Definition

Set the pipe material. Default: custom.

<table data-full-width="false"><thead><tr><th width="132.3173828125"></th><th></th><th></th><th></th><th></th><th data-hidden></th></tr></thead><tbody><tr><td>DN8</td><td>DN10</td><td>DN15</td><td>DN20</td><td>DN25</td><td>尺寸</td></tr><tr><td>SUS 304</td><td>PVC</td><td>PVC</td><td>PVC</td><td>PVC</td><td>預設值</td></tr></tbody></table>

### Notes

1. On certain models, a **“Pipe Material Confirmation”** screen will appear after adjusting **A04, A05, A06, or A07**. If the pipe material is modified on this screen, **A08** will be updated automatically.
2. Each time the pipe material is changed, please re-execute **Z03 Auto Initialize** and **Z04 Auto Zero Offset** to improve measurement accuracy and ensure stable product performance.

### Operation Procedure

<details>

<summary><strong>Button Functions (Click to Expand)</strong></summary>

The main unit has **four buttons**. The **bottom line (Line 3)** of the LCD displays the current function of each button. Under normal operation, the button functions are as follows:

* <img src="https://content.gitbook.com/content/i4ECt41Kyy9211OWazj4/blobs/BZuNjMgY75LH0onY5NtL/image" alt="" data-size="line"> **Blue Button -** Leftmost button: Return, exit, or save settings.

Gray Arrow Buttons:

* <img src="https://content.gitbook.com/content/i4ECt41Kyy9211OWazj4/blobs/Br88VpmnPLAPdutxVdZb/image" alt="" data-size="line"> **Left Gray Button:** Page up, increase value, or select item
* <img src="https://content.gitbook.com/content/i4ECt41Kyy9211OWazj4/blobs/3Dzp8nuxmHsaZ7LqBscw/image" alt="" data-size="line"> **Right Gray Button:** Page down, decrease value, or select item
* <img src="https://content.gitbook.com/content/i4ECt41Kyy9211OWazj4/blobs/sq6fX6r39JE0Au2hahAR/image" alt="" data-size="line"> **Orange Button:** Rightmost button: Enter settings, edit, or confirm selection

{% hint style="danger" %}
**Do not hold buttons for extended periods to avoid damage.**
{% endhint %}

{% hint style="info" %}
Button functions may change depending on the operation context to improve usability or prevent accidental presses.
{% endhint %}

</details>

```
A08 Pipe Material Setting Steps
• From the main screen (green backlight), 
  press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select A. Measurement, press Orange Button (Enter).
• Use Gray Arrow Buttons to select A08 Pipe Material , press Orange Button (Enter).
• Use Gray Arrow Buttons to choose the options. 
• Press Orange Button (Set) to confirm.
• Press Blue Button (ESC) to return to the main screen (green backlight).
```

<figure><img src="https://3404778090-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2Fi4ECt41Kyy9211OWazj4%2Fuploads%2FZEXRayuht6PujsO8t7xy%2FFU-LT-A08-en.png?alt=media&#x26;token=5a52e58b-f4e2-4b7c-990c-e99ac61f5a6a" alt="" width="375"><figcaption></figcaption></figure>

## A08 Options, RS485 Values, Read/Write Commands, and Formats

<table><thead><tr><th>Optionx</th><th>Description</th><th width="206">RS-485 Value</th></tr></thead><tbody><tr><td>Custom</td><td>Custom</td><td>0</td></tr><tr><td>PVCU</td><td></td><td>1</td></tr><tr><td>PVC</td><td></td><td>2</td></tr><tr><td>PP</td><td></td><td>3</td></tr><tr><td>PVDF</td><td></td><td>4</td></tr><tr><td>ABS</td><td></td><td>5</td></tr><tr><td>Steel</td><td></td><td>6</td></tr><tr><td>SUS 304</td><td>Stainless Steel 304</td><td>7</td></tr><tr><td>SUS  316</td><td>Stainless Steel 316</td><td>8</td></tr><tr><td>Copper</td><td></td><td>9</td></tr><tr><td>PFA</td><td></td><td>10</td></tr><tr><td>PE</td><td></td><td>11</td></tr></tbody></table>

> Refer to the [Read/Write Memory List](https://docs.lorric.com/qr/fu-lt-english-v1/communication/modbus-rtu-protocol/read-write-memory-ram) for the Modbus command format. This parameter uses the Int16 data format.