Z02 Auto Pipe Spec

Definition

Automatically detects the pipe specification. This function works the same as A01.

Using patented sensing technology, the system measures the pipe dimensions and automatically selects the closest matching pipe specification from the internal database.

If the measured pipe size differs from standard specifications due to pipe deformation, or if the size is not available in the database, the system will apply a default pipe specification as the pipe size setting. See A02 for reference.

Notes

  • Re-execute this function whenever the device is reinstalled or the pipe size or material is changed.

  • The system compares the sensor’s compression under different pipe specifications with preset pipe data in the database to determine the pipe size.

  • Due to tolerances or other factors, the pipe size matching result may be incorrect.

  • If the pipe size is matched incorrectly, it may cause inaccurate results. Be sure to manually adjust to the correct pipe size by setting A02, A04, A06, and A08.

Operation Procedure

Button Functions (Click to Expand)

When the main screen is displayed in green backlight, the four buttons function as follows:

  • Blue Button (leftmost): Return, exit, or save settings.

  • Gray Direction Buttons:

    • Left Gray: Previous Page, decrease value, or select item

    • Right Gray: Next Page, increase value, or select item

  • Orange Button (rightmost): Rightmost button: Enter settings, edit, or confirm selection

Button functions may change depending on the operation context to improve usability or prevent accidental presses.

Z02 Auto Pipe Spec Setting Steps
• From the main screen (green backlight), 
  press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select Z. Easy Setup, press Orange Button (Enter).
• Use Gray Arrow Buttons to select Z02 Auto Pipe Spec, press Orange Button (Enter).
• Press Right Gray Button to start Auto Pipe Spec.
• Press Blue Button (ESC) to return to the main screen (green backlight).

Last updated