K03 Scale Factor
Definition
Sets the correction method for instantaneous flow. Default: Simple Mode, using the formula:
Corrected Instantaneous Flow = K03 × Measured Instantaneous Flow − K04
Parameters K02 (Correction Mode), K03 (Scale Factor), and K04 (Offset Flow) adjust flowmeter reading deviations.
Notes
K03 cannot accept negative values.
To measure reverse flow, enable A17 (Reverse Flow).
K03 serves the same function as Z05; users may choose either. Executing this function will automatically update the Z05 Scale Factor setting.
Operation Procedure
K02 Options, RS485 Values, Read/Write Commands, and Formats
Parameter Input Range
Corresponding Values
RS-485 Value
Custom
1
-
Minimum
0.001
-
Maximum
1000
-
Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the float32 data format.
Last updated