E08 20mA Value
Definition
Sets the value corresponding to 20 mA on the flow meter. Both positive and negative values are allowed. Default: 100.
Notes
The 20 mA value must be greater than the 4 mA value.
Operation Procedure
E08 20mA Value Setting Steps
• From the main screen (green backlight),
press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select E. Commute , press Orange Button (Enter).
• Use Gray Arrow Buttons to select E08 20mA Value, press Orange Button (Enter).
• Use Gray Arrow Buttons to choose the options.
• Press Orange Button (Set) to confirm.
• Press Blue Button (ESC) to return to the main screen (green backlight).
E08 Options, RS485 Values, Read/Write Commands, and Formats
Parameter Input Range
Corresponding Values
RS-485 Value
Default
100
-
Minimum
-100000
-
Maximum
100000
-
Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the float 32 data format.