D07 Low LIM

Definition

Set the lower limit of the normal flow range. Default: 0. (D05 , D06 , D07 , and D08 work together to enable the flow range over-limit alarm function.)

Flow Range Limit Alarm Example (Click to Expand)
D06 Upper Limit: 30 LPM
D07 Lower Limit: 10 LPM
D08 Hysteresis: 3% (default)

Calculations:
Range: 30 − 10 = 20 LPM
Hysteresis: 20 × 3% = 0.6 LPM

Alarm Behavior:
When flow exceeds the upper limit (30 LPM), the alarm is triggered.
The alarm will clear only when the flow drops below 29.4 LPM (30 − 0.6).
When flow falls below the lower limit (10 LPM), the alarm is triggered.
The alarm will clear only when the flow rises above 10.6 LPM (10 + 0.6).

Notes

If either D06 or D07 is adjusted, the other must also be set; otherwise, the display may not function correctly. If both are unset, default values are D06 = 100, D07 = 0.

Operation Procedure

Button Functions (Click to Expand)

When the main screen is displayed in green backlight, the four buttons function as follows:

  • Blue Button (leftmost): Return, exit, or save settings.

  • Gray Direction Buttons:

    • Left Gray: Previous Page, decrease value, or select item

    • Right Gray: Next Page, increase value, or select item

  • Orange Button (rightmost): Rightmost button: Enter settings, edit, or confirm selection

Button functions may change depending on the operation context to improve usability or prevent accidental presses.

Flow Range Over-Limit Alarm Operation (Click to Expand)

When the flow range alarm is enabled and the flow reaches the alarm condition, Alarm B is triggered. Alarm bits (Bit0, Bit1) display 1 to indicate the alarm has been activated.

The system responds according to the alarm mode set in D05:

  • On: The receiving device receives the alarm signal, and the flow meter screen displays a red backlight warning.

  • Do Not Disturb (DND): The receiving device still receives the alarm signal, but the screen does not display the red backlight.

1

Set D05 to enable the flow range over-limit alarm

D05 FlowLIM Alarm Setting Steps
• From the main screen (green backlight), 
  press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select D. Alarm & Info, press Orange Button (Enter).
• Use Gray Arrow Buttons to select D05 FlowLIM Alarm, press Orange Button (Enter).
• Use Gray Arrow Buttons to choose the options. 
• Press Orange Button (Set) to confirm.
• Press Blue Button (ESC) to return to the main screen (green backlight).
2

Set D06 to define the flow upper limit

D06 Up LIM Setting Steps
• From the main screen(green backlight), 
  press Orange Button(Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select D. Alarm & Info, press Orange Button(Enter).
• Use Gray Arrow Buttons to select D06 Up LIM, press Orange Button(Enter).
• Use Gray Arrow Buttons to choose the digit to adjust(highlighted in dark gray).
• Press Orange Button(Edit) to enter adjustment mode.
• Adjust digits: Left Gray Button to increase, Right Gray Button to decrease.
• Press Orange Button(Set) to confirm each digit; repeat for other digits as needed.
• After all digits are set, press Blue Button(Save).
• Confirm by pressing Orange Button(Save) (or Blue Button(NOT) to cancel).
• Press Blue Button(ESC) to return to the main screen(green backlight).
3

Set D07 to define the flow lower limit

D07 Low LIM Setting Steps
• From the main screen(green backlight), 
  press Orange Button(Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select D. Alarm & Info, press Orange Button(Enter).
• Use Gray Arrow Buttons to select D07 Low LIM, press Orange Button(Enter).
• Use Gray Arrow Buttons to choose the digit to adjust(highlighted in dark gray).
• Press Orange Button(Edit) to enter adjustment mode.
• Adjust digits: Left Gray Button to increase, Right Gray Button to decrease.
• Press Orange Button(Set) to confirm each digit; repeat for other digits as needed.
• After all digits are set, press Blue Button(Save).
• Confirm by pressing Orange Button(Save) (or Blue Button(NOT) to cancel).
• Press Blue Button(ESC) to return to the main screen(green backlight).
4

Set D08 to define the flow hysteresis

D08 Hysteresis Setting Steps
• From the main screen (green backlight), 
  press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select D. Alarm & Info  , press Orange Button (Enter).
• Use Gray Arrow Buttons to select D08 Hysteresis, press Orange Button (Enter).
• Use the Gray Arrow Buttons to adjust the flow hysteresis percentage:
• Press the Left Gray Buttons to increase the value
• Press the Right Gray Buttons to decrease the value
• Press Orange Button (Set) to confirm.
• Press Blue Button (ESC) to return to the main screen (green backlight).
5

Flow Range Over-Limit Alarm Operation

When the flow range alarm is enabled and the flow reaches the alarm condition, Alarm B is triggered. Alarm bits (Bit0, Bit1) display 1 to indicate the alarm has been activated.

The system responds according to the alarm mode set in D05:

  • On: The receiving device receives the alarm signal, and the flow meter screen displays a red backlight warning.

  • Do Not Disturb (DND): The receiving device still receives the alarm signal, but the screen does not display the red backlight.

D07 Options, RS485 Values, Read/Write Commands, and Formats

Parameter Input Range
Corresponding Values
RS-485 Value

Default

0

-

Minimum

-100000

-

Maximum

99999

-

Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the float 32 data format.