A18 Low Flow Cutoff
Definition
This function forces the flowmeter to display flow values below a set threshold as 0. The default value is 0, which disables the function.
When A18 Low Flow Cutoff is disabled, small near-zero measurement fluctuations may be displayed, causing slight value variations when the system is stopped.
To display a stable zero flow when the system is stopped, enable A18 to force flow values below the threshold to zero, preventing zero drift and minor measurement disturbances.
Notes
The default value is 0, which means the function is disabled and the flowmeter will display actual small flow values.
The condition “below the set value” is evaluated using the absolute value of the flow rate. Regardless of forward or reverse flow, any value lower than the set threshold will be displayed as 0.
A18 is a hard cutoff for both display and output. When the actual flow rate is lower than the A18 setting, the flowmeter will display 0 and no flow variation within this range will be output.
If the application requires measurement of small flow fluctuations near zero, the measured flow value must be greater than the A18 setting. Otherwise, the flow will be treated as 0 and cannot be measured or recorded.
Setting Recommendations
General process display / PLC false-trigger prevention: Set A18 close to the lower measurement limit of the flowmeter model to improve zero stability.
Low-flow detection / micro-flow research applications: It is recommended to disable A18 (A18 = 0) to preserve full measurement information near zero flow.
*Lower measurement limit
Pipe Size
DN15
DN20
DN25
DN32
DN40
DN50
DN65
DN75
Lower measurement limit
1.5 LPM
2 LPM
3 LPM
5 LPM
8 LPM
13 LPM
22 LPM
30 LPM
Operation Procedure
Button Functions (Click to Expand)
When the main screen is displayed in green backlight, the four buttons function as follows:
Blue Button (leftmost): Return, exit, or save settings.
Gray Direction Buttons:
Left Gray: Previous Page, decrease value, or select item
Right Gray: Next Page, increase value, or select item
Orange Button (rightmost): Rightmost button: Enter settings, edit, or confirm selection
Do not hold buttons for extended periods to avoid damage.
Button functions may change depending on the operation context to improve usability or prevent accidental presses.

A18 Options, RS485 Values, Read/Write Commands, and Formats
Custom
0
-
Minumum
0
-
Maximum
150,000,000
-
Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the float 32 data format.