F Simulate

F Simulate parameter list

Serial number

Name

Function

F01

Sim. Volume (Simulation Volume)

Set up simulate value of instantaneous flow speed, the unit will be the one set in parameter group B.

F02

Sim. Mode (Simulation Mode)

Simulation function will be activated after selecting “ on ”, default off.

OCT (besides pulse), RS485 and Analog current output will be operated according to the changes of simulated data and cumulative flow.

Please be noted that cumulative flow and history data will be affected.

Simulate mode will be reminded on the screen.

The corresponding communication function will work normally only after being turned on.

F03

Sim. PulseHz (Simulation PulseHz)

Under this page, pulse signal will be outputted according to set frequency within value 0 to 700. Please set up NC/NO of pulse according to parameter E01, and pulse width according to parameter E03.

It operates whether OCT info is turned on or not.

The video about F parameter setup.

Watch the video or scan the the QR code below. (*Please refer to the parameter list of this version of the manual for the new and modified parameters)