E14 PulseV2 Unit
Definition
Defines the flow rate corresponding to one pulse output from the flow meter.
Notes
To enable the pulse function, set E02 OCT Definition to “Pulse v2”, configure the pulse width in E03 Pulse Time, set the forward flow unit in B01, and define the pulse output reference unit in E14 Pulse v2 Unit.
The instantaneous flow unit set in B01.
The pulse output reference unit set in E14.
Description
L or m³
Liter
When B01 is set to Liters or Cubic Meters, the E14 pulse output reference unit is always Liters.
U.gal or ft³
U.gal
When B01 is set to US Gallons or Cubic Feet, the E14 pulse output reference unit is always US Gallons.
I.gal
I.gal
When B01 is set to Imperial Gallons, the E14 pulse output reference unit is Imperial Gallons.
Operation Procedure

E14 Options, RS485 Values, Read/Write Commands, and Formats
0.02 unit (Default)
Outputs 1 pulse for every 0.02 of the reference unit.
1
0.03 unit
Outputs 1 pulse for every 0.03 of the reference unit.
2
0.05 unit
Outputs 1 pulse for every 0.05 of the reference unit.
3
0.07 unit
Outputs 1 pulse for every 0.07 of the reference unit.
4
0.1 unit
Outputs 1 pulse for every 0.1 of the reference unit.
5
0.2 unit
Outputs 1 pulse for every 0.2 of the reference unit.
6
0.3 unit
Outputs 1 pulse for every 0.3 of the reference unit.
7
0.5 unit
Outputs 1 pulse for every 0.5 of the reference unit.
8
0.7 unit
Outputs 1 pulse for every 0.7 of the reference unit.
9
1 unit
Outputs 1 pulse for every 1 of the reference unit.
10
5 unit
Outputs 1 pulse for every 5 of the reference unit.
13
10 unit
Outputs 1 pulse for every 10 of the reference unit.
17
50 unit
Outputs 1 pulse for every 50 of the reference unit.
18
100 unit
Outputs 1 pulse for every 100 of the reference unit.
19
Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the Unsigned Int16 (UINT16) data format.