E13 Iout Range
Definition
Defines the output range of the flow meter’s analog signal. Default: 4–20 mA.
Notes
Modifying this setting affects the options in E09 Iout Error. After making changes, verify that E09 is configured according to your requirements.
Operation Procedure
E13 Analog Output Range Setting Steps
• From the main screen (green backlight),
press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select E. Commute , press Orange Button (Enter).
• Use Gray Arrow Buttons to select E13 Analog Output, press Orange Button (Enter).
• Use Gray Arrow Buttons to choose the options.
• Press Orange Button (Set) to confirm.
• Press Blue Button (ESC) to return to the main screen (green backlight).
E13 Options, RS485 Values, Read/Write Commands, and Formats
Option
Description
RS-485 Value
0 -20mA
4 - 20 mA (Default)
0
Refer to the Read/Write Memory List for the Modbus command format. This parameter uses the Unsigned Int16 (UINT16) data format.