D Alarm & Info
D Alarm & Information Parameter List
Serial number
Name
Function
D01
Paddle Ala.
(Paddle Alarm)
Alarm - A
Alarm of paddle wheel error. Default on, but can be turned off.
D02
Mag. Ala.
(Magnetic Alarm)
Alarm - A
Alarm when interference from an external magnetic field. Default on, but can be turned off.
D03
Bat. Alarm (Battery Alarm)
Alarm - C
Alarm when CR2032 battery is going to be out of battery. Default on, but can be turned off. Attention: Take out the battery and wait one minute, the battery alarm will be displayed.
D04
FlowLIM Ala (Flow Volume Limit Alarm)
Alarm - B
Alarm when instantaneous flow is out of range. Default on, but can be turned off.
D05
Up LIM
(Upper Limit)
Define D04 upper limit of normal flow range.
D06
Low LIM
(Lower Limit)
Define D04 lower limit of normal flow range.
D07
Hysteresis% (Hysteresis Percentage)
For setting the hysteresis range of turning off alarm.
The Percentage is the proportion of the range between upper and lower limit.
The range is 0-33%, default 3%.
This parameter needs to be positive value.
D08
Total Ala.
(Total Alarm)
Alarm - B
Alarm when cumulative flow is out of range. Default on, but can be turned off.
D09
Total Trig.
(Total Alarm Trigger Condition)
Set-up the target cumulative value alarm condition. Option "greater than" target or "less than" target . Default "greater than" target.
D10
Total Target
Set up alarm target value of cumulative flow speed.
D11
Iout Alarm
Alarm B
Alarm when it exceeds 4-20mA range. Default on, but can be turned off.
D12
Speed Alarm
Alarm B
Alarm when flow speed exceeds 10m/s. Default on, but can be turned off.
D13
PulseOverlap
Alarm B
Alarm for Pulse Output signal overlaps caused by too long pulse width time parameter E03. Default on, but can be turned off.
D14
IoutStatAla
(Iout Status Alarm)
Set Iout status alarm mode. The options are ''on'', ''off'' and ''do not disturb.'' The default setting is ''do not disturb''. It means that when an abnormality occurs, the color and LED displayed on the screen will not change. The number can still be displayed in the communication part, and the bit will show an abnormality on the status page. (Since FW2.2.0 new function)