Read/Write Memory – Read List

When reading large values with different data formats (e.g., Float32), tiny differences may occur due to internal calculations, typically less than 1/10,000, which is normal.

Read commands must not exceed 20 registers; longer requests will be ignored. See the register list for details.

How to Use the Read/Write Memory List

Field Name
Function

Register Address

Addresses for read/write memory, not shared with read-only memory.

Register Length

Length of the register variable.

Memory Content Name

Describes the name or purpose of the memory content. Linked names go to that parameter's own page for full option values, ranges, and setup steps.

Data Type

Specifies the format of transmitted or received data.

Read Command

Indicates the available read commands.

Write Command

Indicates the available write commands. A value of X in this column means remote writing is not supported for that register.

Read-Write Memory List

Register Address
Decimal
Master Address
Reg Length
Memory Content Name
Data Type
Read Command
Write Command

0x0000

0

40001

1

unsigned int 16

03

06

0x0001

1

40002

2

float 32

03

30

0x0003

3

40004

1

unsigned int 16

03

06

0x0004

4

40005

1

unsigned int 16

03

06

0x0005

5

40006

1

unsigned int 16

03

06

0x0006

6

40007

1

unsigned int 16

03

06

0x0007

7

40008

1

unsigned int 16

03

06

0x0008

8

40009

1

unsigned int 16

03

06

0x0100

256

40257

1

unsigned int 16

03

06

0x0101

257

40258

1

unsigned int 16

03

06

0x0102

258

40259

1

unsigned int 16

03

06

0x0103

259

40260

1

unsigned int 16

03

06

0x0104

260

40261

1

unsigned int 16

03

06

0x0200

512

40513

1

unsigned int 16

03

06

0x0201

513

40514

1

unsigned int 16

X

06

0x0202

514

40515

1

unsigned int 16

03

06

0x0203

515

40516

1

unsigned int 16

X

06

0x0300

768

40769

1

unsigned int 16

03

06

0x0301

769

40770

1

unsigned int 16

03

06

0x0302

770

40771

1

unsigned int 16

03

06

0x0303

771

40772

1

unsigned int 16

03

06

0x0304

772

40773

2

float 32

03

30

0x0306

774

40775

2

float 32

03

30

0x0308

776

40777

1

unsigned int 16

03

06

0x0309

777

40778

1

unsigned int 16

03

06

0x030A

778

40779

1

unsigned int 16

03

06

0x030B

779

40780

2

float 32

03

30

0x030D

781

40782

1

unsigned int 16

03

06

0x030E

782

40783

1

unsigned int 16

03

06

0x030F

783

40784

1

unsigned int 16

03

06

0x0400

1024

41025

1

unsigned int 16

03

06

0x0401

1025

41026

1

unsigned int 16

03

06

0x0402

1026

41027

1

unsigned int 16

03

06

0x0403

1027

41028

1

unsigned int 16

03

06

0x0404

1028

41029

1

unsigned int 16

03

06

0x0405

1029

41030

1

unsigned int 16

03

06

0x0406

1030

41031

2

float 32

03

30

0x0408

1032

41033

2

float 32

03

30

0x040A

1034

41035

1

unsigned int 16

03

06

0x040B

1035

41036

2

float 32

03

30

0x040D

1037

41038

2

float 32

03

30

0x040F

1039

41040

1

unsigned int 16

03

06

0x0410

1040

41041

1

unsigned int 16

03

06

0x0500

1280

41281

2

float 32

03

30

0x0502

1282

41283

1

sim on – reserved

const

03

X

0x0503

1283

41284

1

sim pulse – reserved

const

03

X

0x0600

1536

41537

1

unsigned int 16

03

06

0x0601

1537

41538

1

unsigned int 16

03

06

0x0602

1538

41539

1

unsigned int 16

03

06

0x0603

1539

41540

1

unsigned int 16

03

06

0x0604

1540

41541

1

unsigned int 16

03

06

0x0700

1792

41793

1

unsigned int 16

03

06

0x0701

1793

41794

1

unsigned int 16

03

06

0x0702

1794

41795

1

unsigned int 16

03

06

0x0703

1795

41796

1

unsigned int 16

03

06

0x0704

1796

41797

1

unsigned int 16

X

06

0x0705

1797

41798

1

unsigned int 16

X

06

0x0706

1798

41799

1

unsigned int 16

03

06

0x0707

1799

41800

1

unsigned int 16

03

06

Example: C02 Del. Total (clear/reset totalized flow)

Step
Value

Table Register Address (Hex)

0x0201

Converted to decimal

0x0201 = 2×256 + 1 = 513

Master address to enter (4xxxx convention)

40001 + 513 = 40514

Address bytes in the frame

02 01

Full write frame (station 01)

01 06 02 01 00 01 18 72

If 40201 is entered by mistake, the master sends decimal 200 (0x00C8) — an address that doesn't exist. The flow meter won't respond, or may return exception code 02; on the PLC side this appears as "no response to write."

Self-verification tip

If you're not sure which address convention your master uses, first use function code 03 to read the register that corresponds to Modbus ID. If the value read back matches the device's own station number, the address base is correct and you can safely apply the same convention to the other addresses.