Read-Only Memory (ROM) – List
Memory Location and Definition
How to use the tables on this page:
Field Names
Functions
Register Address (Hex)
The two bytes that actually appear in the communication frame. Use this for building frames directly, or for 0-based masters (e.g. CODESYS, pymodbus).
Decimal
The decimal value of the protocol address. For 1-based debug software (e.g. Modbus Poll, Modscan), add 1 to this value.
Master Address (Convention)
The value to enter directly into PLC/HMI configuration screens — Siemens S7-200 SMART / S7-1200, Delta, Weintek, etc.
Register Length
The length of the variable, in units of Registers (2 bytes each).
Memory Content
Description of the function or purpose of the memory.
Data Type
Specifies the format of the transmitted or received data.
Read-Only Memory List
0x0000
0
30001
2
instantaneous flow rate
float 32
0x0002
2
30003
2
instantaneous flow velocity
float 32
0x0004
4
30005
2
totalized flow volume
float 32
0x0006
6
30007
2
analog output in micro-amp
unsigned int 32
0x000D
13
30014
1
history[1] year & month
unsigned int 16
0x000E
14
30015
1
history[1] day
unsigned int 16
0x000F
15
30016
1
history[1] total method
unsigned int 16
0x0010
16
30017
2
history[1] totalized flow volume
float32
0x0012
18
30019
1
history[2] year & month
unsigned int 16
0x0013
19
30020
1
history[2] day
unsigned int 16
0x0014
20
30021
1
history[2] total method
unsigned int 16
0x0015
21
30022
2
history[2] totalized flow volume
float32
0x0017
23
30024
1
history[3] year & month
unsigned int 16
0x0018
24
30025
1
history[3] day
unsigned int 16
0x0019
25
30026
1
history[3] total method
unsigned int 16
0x001A
26
30027
2
history[3] totalized flow volume
float32
0x001C
28
30029
1
history[4] year & month
unsigned int 16
0x001D
29
30030
1
history[4] day
unsigned int 16
0x001E
30
30031
1
history[4] total method
unsigned int 16
0x001F
31
30032
2
history[4] totalized flow volume
float32
0x0021
33
30034
1
history[5] year & month
unsigned int 16
0x0022
34
30035
1
history[5] day
unsigned int 16
0x0023
35
30036
1
history[5] total method
unsigned int 16
0x0024
36
30037
2
history[5] totalized flow volume
float32
0x0026
38
30039
1
history[6] year & month
unsigned int 16
0x0027
39
30040
1
history[6] day
unsigned int 16
0x0028
40
30041
1
history[6] total method
unsigned int 16
0x0029
41
30042
2
history[6] totalized flow volume
float32
0x002B
43
30044
1
history[7] year & month
unsigned int 16
0x002C
44
30045
1
history[7] day
unsigned int 16
0x002D
45
30046
1
history[7] total method
unsigned int 16
0x002E
46
30047
2
history[7] totalized flow volume
float32
0x0030
48
30049
1
history[8] year & month
unsigned int 16
0x0031
49
30050
1
history[8] day
unsigned int 16
0x0032
50
30051
1
history[8] total method
unsigned int 16
0x0033
51
30052
2
history[8] totalized flow rate
float32
0x0035
53
30054
1
history[9] year & month
unsigned int 16
0x0036
54
30055
1
history[9] day
unsigned int 16
0x0037
55
30056
1
history[9] total method
unsigned int 16
0x0038
56
30057
2
history[9] totalized flow rate
float32
0x003A
58
30059
1
history[10] year & month
unsigned int 16
0x003B
59
30060
1
history[10] day
unsigned int 16
0x003C
60
30061
1
history[10] total method
unsigned int 16
0x003D
61
30062
2
history[10] totalized flow rate
float32
0x003F
63
30064
1
history[11] year & month
unsigned int 16
0x0040
64
30065
1
history[11] day
unsigned int 16
0x0041
65
30066
1
history[11] total method
unsigned int 16
0x0042
66
30067
2
history[11] totalized flow rate
float32
0x0044
68
30069
1
history[12] year & month
unsigned int 16
0x0045
69
30070
1
history[12] day
unsigned int 16
0x0046
70
30071
1
history[12] total method
unsigned int 16
0x0047
71
30072
2
history[12] totalized flow rate
float32
0x0049
73
30074
1
history[13] year & month
unsigned int 16
0x004A
74
30075
1
history[13] day
unsigned int 16
0x004B
75
30076
1
history[13] total method
unsigned int 16
0x004C
76
30077
2
history[13] totalized flow rate
float32
0x004E
78
30079
1
history[14] year & month
unsigned int 16
0x004F
79
30080
1
history[14] day
unsigned int 16
0x0050
80
30081
1
history[14] total method
unsigned int 16
0x0051
81
30082
2
history[14] totalized flow rate
float32
0x0053
83
30084
1
Maximum r value
unsigned int 16
0x0054
84
30085
1
Minimum r value
unsigned int 16
0x0055
85
30086
2
instantaneous flow rate
signed int 32
Value is instantaneous flow rate ×100, rounded to integer
0x0057
87
30088
2
instantaneous flow speed
signed int 32
Value is instantaneous flow speed ×100, rounded to integer
0x0059
89
30090
2
totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x005B
91
30092
2
history[1] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x005D
93
30094
2
history[2] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x005F
95
30096
2
history[3] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x0061
97
30098
2
history[4] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x0063
99
30100
2
history[5] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x0065
101
30102
2
history[6] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x0067
103
30104
2
history[7] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x0069
105
30106
2
history[8] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x006B
107
30108
2
history[9] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x006D
109
30110
2
history[10] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x006F
111
30112
2
history[11] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x0071
113
30114
2
history[12] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x0073
115
30116
2
history[13] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer
0x0075
117
30118
2
history[14] totalized flow rate
signed int 32
Value is totalized flow rate ×100, rounded to integer