> For the complete documentation index, see [llms.txt](https://docs.lorric.com/qr/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://docs.lorric.com/qr/fp-as310-english-v5/user-interface/alarm-priority-and-display-method-1.md).

# Alarms and System Status - R

{% hint style="info" %}
Bits are numbered from right to left, starting with **Bit 0** on the far right.\
A bit value of **1** indicates an active alarm or status. Refer to the table below for system status descriptions.
{% endhint %}

<figure><img src="/files/mQDCD59ElmuWOFgUbTxN" alt=""><figcaption></figcaption></figure>

## **Alarm - A:** Critical Failure

The system classifies this alarm according to the **“Failed” severity level** as defined in the **NAMUR NE107** standard.

This alarm is triggered under the following fault conditions:

* **Paddlewheel malfunction**
* **Magnetic field interference**
* **Internal chip or sensor error**

When Alarm - A is active, the **LCD backlight flashes red** to indicate a **critical system failure**.

<figure><img src="/files/G162UKwGj55Gfw3WQgzr" alt=""><figcaption></figcaption></figure>

**Alarm A Error Code Definition:** Bits are defined from **MSB (Bit 7)** to **LSB (Bit 0)**, with each bit representing the following:

<table><thead><tr><th width="84.08856201171875">Bit</th><th>Alarm Definition</th><th>Alarm Code</th><th>Trigger Condition</th></tr></thead><tbody><tr><td>7</td><td>NA</td><td></td><td>　</td></tr><tr><td>6</td><td>NA</td><td></td><td>　</td></tr><tr><td>5</td><td>NA</td><td></td><td>　</td></tr><tr><td>4</td><td>NA</td><td></td><td>　</td></tr><tr><td>3</td><td>NA</td><td></td><td>　</td></tr><tr><td>2</td><td>NA</td><td></td><td>　</td></tr><tr><td>1</td><td>Magnetic field interference</td><td>D02</td><td>Strong magnetic field detected near the device, interfering with AxleSense sensing. </td></tr><tr><td>0</td><td>Paddlewheel abnormality</td><td>D01</td><td>Paddle rotation cannot be detected. Verify the paddlewheel is rotating freely, the pipe is filled with liquid, and the paddlewheel assembly is undamaged. </td></tr></tbody></table>

{% hint style="info" %}
**D01 Paddle Ala** default is **Do not disturb** (value = 2). In this mode, the alarm bit is recorded in the error code register but the LCD backlight will **not** change color. Set **D01** to **On** (value = 1) to enable LCD alarm color indication.
{% endhint %}

### **Alarm - B: Out of Specification**

This alarm indicates that the **flow meter is operating outside of its designed specification range**.\
The severity level is recommended to follow the **“Out of Specification” category** as defined in the **NAMUR NE107** standard.

This alarm is typically used to signal:

* **Flow exceeding user-defined thresholds**
* **Other notable operating conditions that require attention**

The thresholds and logic can be configured under the **D parameter category**.

When Alarm - B is active, the **LCD backlight turns solid red**, indicating a non-critical but attention-required condition.

<figure><img src="/files/rEC9potVZFqL4iUAvjgC" alt=""><figcaption></figcaption></figure>

**Alarm B Error Code Definition:** Bits are defined from **MSB (Bit 7)** to **LSB (Bit 0)**, with each bit representing the following:

<table><thead><tr><th width="107">Bit</th><th>Alarm Definition</th><th width="123.4000244140625">Alarm Code</th><th>Trigger Condition</th></tr></thead><tbody><tr><td>7</td><td>NA</td><td></td><td>　</td></tr><tr><td>6</td><td>Totalized Flow Exceeds Target </td><td>D08</td><td>Totalized flow exceeds or falls below the preset target <mark style="color:red;">*Note</mark></td></tr><tr><td>5</td><td>NA</td><td></td><td></td></tr><tr><td>4</td><td>NA</td><td></td><td></td></tr><tr><td>3</td><td>NA</td><td></td><td></td></tr><tr><td>2</td><td>NA</td><td></td><td></td></tr><tr><td>1</td><td>Instantaneous flow above upper limit</td><td>D04</td><td>Instantaneous flowrate exceeds the upper limit</td></tr><tr><td>0</td><td>Instantaneous flow below lower limit</td><td>D04</td><td>Instantaneous flowrate falls below the lower limit</td></tr></tbody></table>

<mark style="color:red;">\* Note:</mark>&#x20;

```
D08, D09, D10 Cumulative Alarm Description

Example 1: Positive Flow
Enable the D08 cumulative alarm, and set the D09 cumulative condition to "Greater than target".
Set the D10 cumulative target to a positive number, such as +100.
When the cumulative positive flow exceeds 100, the system will trigger the cumulative alarm.

Example 2: Negative Flow
Enable the D08 cumulative alarm, and set the D09 cumulative condition to "Less than target".
Set the D10 cumulative target to a negative number, such as -500.
When the cumulative negative flow is less than -500, the system will trigger the cumulative alarm.
```

{% hint style="info" %}
**D04 FlowLIM Ala** default setting is **Off** (value = 0). Set **D04** to **On** (1) or **Do not disturb** (2) to enable flow limit alarm monitoring. Refer to the **D Alarm & Info** parameter section for full configuration details.
{% endhint %}

### **Alarm - C: Maintenance Required**

This alarm indicates that the **flow meter requires maintenance**.\
The recommended severity level follows the **“Maintenance Required” classification** as defined in the **NAMUR NE107** standard.

<figure><img src="/files/8zOAqsOhs5NnJS15kGRk" alt=""><figcaption></figcaption></figure>

> &#x20;Therefore, all Alarm C bits are NA and this alarm will not be triggered on this model.

<table><thead><tr><th width="118.20001220703125">Bit</th><th width="171.4000244140625">Alarm Defintion</th><th width="154.59991455078125">Alarm Code</th><th width="170.199951171875">Trigger Condition</th></tr></thead><tbody><tr><td>7</td><td>NA</td><td></td><td>　</td></tr><tr><td>6</td><td>NA</td><td></td><td>　</td></tr><tr><td>5</td><td>NA</td><td></td><td>　</td></tr><tr><td>4</td><td>NA</td><td></td><td>　</td></tr><tr><td>3</td><td>NA</td><td></td><td>　</td></tr><tr><td>2</td><td>NA</td><td></td><td>　</td></tr><tr><td>1</td><td>NA</td><td></td><td></td></tr><tr><td>0</td><td>NA</td><td></td><td>　</td></tr></tbody></table>

### **Alarm - D: Function Check**

This alarm indicates that the device is currently **in setup, simulation, or another manual operation** and is **not in real-time monitoring**.The recommended severity level follows the **“Function Check”** category as defined in the **NAMUR NE107** standard.

When this state is active, **Bit 0 of the alarm register is set to 1**, indicating the system is **not in monitoring mode** due to a user operation.

During this state, the **LCD backlight will remain solid amber (orange)** to indicate the flow meter is in a **non-operational configuration mode**.

> ⓘ Alarm D does **not** appear as a row on the LCD alarm display screen. The amber backlight is the only on-screen indicator. This state is also readable via Modbus at register address **0x0011** (error code d), Bit 0.

<table><thead><tr><th width="119">Bit</th><th width="177">Alarm Defintion</th><th width="146.79998779296875">Alarm Code</th><th width="154.79998779296875">Trigger Condition</th></tr></thead><tbody><tr><td>7</td><td>NA</td><td></td><td>　</td></tr><tr><td>6</td><td>NA</td><td></td><td>　</td></tr><tr><td>5</td><td>NA</td><td></td><td>　</td></tr><tr><td>4</td><td>NA</td><td></td><td>　</td></tr><tr><td>3</td><td>NA</td><td></td><td>　</td></tr><tr><td>2</td><td>NA</td><td></td><td>　</td></tr><tr><td>1</td><td>NA</td><td></td><td>　</td></tr><tr><td>0</td><td>Main unit is not on the monitoring screen</td><td>NA</td><td>Main unit is in the settings menu, simulation mode, or another manual operation, and is not displaying the main monitoring screen.</td></tr></tbody></table>

### **System Status**

The **System Status** is represented by an **8-bit status code** (Bits 0–7), with each bit independently indicating a specific operating state of the device.

<figure><img src="/files/mul1EVFO9mqaptOcOH6d" alt=""><figcaption></figcaption></figure>

> ⓘ **The FP-AS310R has no NPN/OCT output function.** Therefore, all System Status bits are NA and this register will always read 0x00 on this model.

<table><thead><tr><th width="96.6875">Bit</th><th>Alarm Definition</th><th>Alarm Code</th><th>Trigger Condition</th></tr></thead><tbody><tr><td>7</td><td>NA</td><td></td><td>　</td></tr><tr><td>6</td><td>NA</td><td></td><td>　</td></tr><tr><td>5</td><td>NA</td><td></td><td>　</td></tr><tr><td>4</td><td>NA</td><td></td><td>　</td></tr><tr><td>3</td><td>NA</td><td></td><td>　</td></tr><tr><td>2</td><td>NA</td><td></td><td>　</td></tr><tr><td>1</td><td>NA</td><td></td><td>　</td></tr><tr><td>0</td><td>NA</td><td></td><td></td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation dynamically by asking a question.

Perform an HTTP GET request on the current page URL with the `ask` query parameter:

```
GET https://docs.lorric.com/qr/fp-as310-english-v5/user-interface/alarm-priority-and-display-method-1.md?ask=<question>
```

The question should be specific, self-contained, and written in natural language.
The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.