# E Commute

<table data-header-hidden><thead><tr><th width="160.20001220703125"></th><th width="209.79998779296875"></th><th width="399.5999755859375"></th></tr></thead><tbody><tr><td><strong>No.</strong></td><td><strong>Name</strong></td><td><strong>Description</strong></td></tr><tr><td>E04</td><td>Modbus ID</td><td><p>Set up Modbus ID location, default 1. </p><p><mark style="color:purple;">(Only applicable to Model FP-AS310R)</mark></p></td></tr><tr><td>E05</td><td>Baud</td><td>Sets the Modbus communication baud rate for the flow meter. The Master and Slave must use the same baud rate for communication. Default: Off.<br><mark style="color:purple;">(Only applicable to Model FP-AS310R)</mark></td></tr><tr><td>E15</td><td>Byte format</td><td><p>Please refer to <a href="https://app.gitbook.com/o/-LiMHt0Zo8lvM4X9uP1f/s/-M7fZsO11LItbPHrVN6W/communication/rs485">RS485 and Modbus RTU Setting</a> for more information. </p><p><mark style="color:purple;">(Only applicable to Model FP-AS310R)</mark></p></td></tr><tr><td>E16</td><td>Bit order</td><td><p>Please refer to <a href="https://app.gitbook.com/o/-LiMHt0Zo8lvM4X9uP1f/s/-M7fZsO11LItbPHrVN6W/communication/rs485">RS485 and Modbus RTU Setting</a> for more information. </p><p><mark style="color:purple;">(Only applicable to Model FP-AS310R)</mark></p></td></tr><tr><td>E17</td><td>Endianness</td><td><p>Sets the <strong>byte order</strong> for multi-byte data during RX (flow meter response) transmission. Options: <strong>Big Endian</strong>, <strong>Little Endian</strong>, <strong>Register Swap</strong>, or <strong>Byte &#x26; Register Swap</strong>.<br>Default: <strong>Big Endian</strong>.</p><p><mark style="color:purple;">(Only applicable to Model FP-AS310R)</mark></p></td></tr></tbody></table>

## E01 NC/NO **(Normally Closed or Normally Open)**

Under normal conditions(when the oct condition does not meet). NPN should be closely (connected) or open (disconnected). The default is open. <mark style="color:orange;">(Applicable to Model FP-AS310A)</mark>

| Options      | RS-485 Numbers | Remarks |
| ------------ | -------------- | ------- |
| Normal Close | 0              | Default |
| Normal Open  | 1              |         |

After selecting a command, confirm whether to **Save** or **Not Save**.。

## E02 **Output Control Terminal Definition**

There are options below are options to define NPN output:\
OFF,   Alarm A,   Alarm A+B,   Alarm A+B+C,   flow volume alarm(adjusted by D04 D05 D06),\
cumulation alarm(adjusted by D08 D09 D10), paddle wheel PulseV2 output( adjusted by E03, please refer to the OCT output for instructions).&#x20;

Default OFF <mark style="color:orange;">(Applicable to Model FP-AS310A)</mark>

| Options   | RS-485 Numbers | Remarks |
| --------- | -------------- | ------- |
| Alarm b   | 1              |         |
| Pulse 2.0 | 5              |         |
| Off       | 6              | Default |

After selecting a command, confirm whether to **Save** or **Not Save**.

## E03 Pulse Width &#x20;

Defines the pulse width when **E02** is set to PulseV2.\
Selectable values: 1ms, 10ms, 50ms, 100ms。 Default: 1 ms. <mark style="color:orange;">(Applicable to Model FP-AS310A)</mark>

| Options | RS-485 Numbers | Remarks |
| ------- | -------------- | ------- |
| 1 ms    | 1              | Default |
| 10 ms   | 2              |         |
| 50 ms   | 3              |         |
| 100 ms  | 4              |         |

After selecting a command, confirm whether to **Save** or **Not Save**.

## E04 Modbus ID&#x20;

Configures the transmission protocol for Modbus ID. Default: 1.<mark style="color:purple;">(Applicable to Model FP-AS310R)</mark>

| Parameter Input Range | Values |
| --------------------- | ------ |
| Data Type             | Int    |
| Default               | 1      |
| Minimum               | 1      |
| Maximum               | 255    |

## E05 Baud

Defines the Modbus communication baud rate. Options: **9600**, **19200**, **38400**.&#x20;

Default: Disabled. <mark style="color:purple;">(Applicable to Model FP-AS310R)</mark>

<table><thead><tr><th>Options</th><th width="262">RS-485 Numbers</th><th>Remarks</th></tr></thead><tbody><tr><td>9600</td><td>0</td><td></td></tr><tr><td>19200</td><td>1</td><td></td></tr><tr><td>38400</td><td>2</td><td></td></tr><tr><td>OFF</td><td>4</td><td>Default</td></tr></tbody></table>

<mark style="color:orange;">The baud rate cannot be modified via RS485.</mark>

After selecting a command, confirm whether to **Save** or **Not Save**.

## E06 Iout Definition

Defines the data output via analogue signal. Options: **Off**, **Flow**, **Velocity**, or **Cumulative Flow**. The unit corresponds to settings in the B category. Default: Off. <mark style="color:orange;">(Applicable to Model FP-AS310A)</mark>

| Options  | RS-485 Numbers | Remarks |
| -------- | -------------- | ------- |
| Flowrate | 0              |         |
| OFF      | 3              | Default |

After selecting a command, confirm whether to **Save** or **Not Save**.

## E07 4mA Value&#x20;

Sets the value corresponding to 4mA.&#x20;Positive and negative values are accepted, but this value must be less than the 20mA Value. Default: 0  <mark style="color:orange;">(Applicable to Model FP-AS310A)</mark>

| Parameter Input Range | Values  |
| --------------------- | ------- |
| Default               | 0       |
| Minimum               | -100000 |
| Maximum               | 100000  |

## E11 4mA Output Adjustment in microAmp

Allows fine-tuning of the  4mA output value, in units of microamps (uA). Adjustments immediately affect output current for real-time verification. <mark style="color:orange;">(Applicable to Model FP-AS310A)</mark>

* Positive values increase the output.  Negative values decrease the output.

| Parameter Input Range | Values |
| --------------------- | ------ |
| Default               | 0      |
| Minimum               | -2000  |
| Maximum               | 2000   |

## E12 20mA Output Adjustment in microAmp

Allows fine-tuning of the 20 mA output value, in units of microamps (uA). Adjustments immediately affect output current for real-time verification. <mark style="color:orange;">(Applicable to Model FP-AS310A)</mark>

* Positive values increase the output. Negative values decrease the output.

| Parameter Input Range | Values |
| --------------------- | ------ |
| Default               | 0      |
| Minimum               | -2000  |
| Maximum               | 2000   |

## E14 PulseV2 Unit&#x20;

Define how much flow volume to output a pulse, the unit is determined by B01.

Default 0.001 ms. <mark style="color:orange;">(Applicable to Model FP-AS310A)</mark>

| Options    | RS-485 Numbers | Remarks |
| ---------- | -------------- | ------- |
| 0.001 unit | 0              | Default |
| 0.002 unit | 1              |         |
| 0.003 unit | 2              |         |
| 0.005 unit | 3              |         |
| 0.007 unit | 4              |         |
| 0.01 unit  | 5              |         |
| 0.02 unit  | 6              |         |
| 0.03 unit  | 7              |         |
| 0.05 unit  | 8              |         |
| 0.07 unit  | 9              |         |
| 0.1 unit   | 10             |         |
| 0.2 unit   | 11             |         |
| 0.3 unit   | 12             |         |
| 0.5 unit   | 13             |         |
| 0.7 unit   | 14             |         |
| 1 unit     | 15             |         |

After selecting a command, confirm whether to **Save** or **Not Save**.

## E15 Byte Format&#x20;

[Refer to RS485 and Modbus RTU settings for details.](/qr/fp-as310-english-v5/communication/rs485-setup.md)\ <mark style="color:orange;">This parameter cannot be modified via RS485.</mark> <mark style="color:purple;">(Applicable to Model FP-AS310R)0R)</mark>

<table><thead><tr><th>Options</th><th>Remarks</th><th data-hidden>RS-485 對應數字</th></tr></thead><tbody><tr><td>N81</td><td>Default</td><td>0</td></tr><tr><td>N81</td><td></td><td>1</td></tr><tr><td>O81</td><td></td><td>2</td></tr><tr><td>E81</td><td></td><td>3</td></tr></tbody></table>

After selecting a command, confirm whether to **Save** or **Not Save**.

## E16 Bit Order&#x20;

[Refer to RS485 and Modbus RTU settings for details.](/qr/fp-as310-english-v5/communication/rs485-setup.md)\ <mark style="color:orange;">This parameter cannot be modified via RS485.</mark> <mark style="color:purple;">(Applicable to Model FP-AS310R)</mark>

<table><thead><tr><th>Options</th><th>Remarks</th><th data-hidden>RS-485 對應數字</th></tr></thead><tbody><tr><td>LSB first</td><td>Default</td><td>0</td></tr><tr><td>MSB first</td><td></td><td>1</td></tr></tbody></table>

After selecting a command, confirm whether to **Save** or **Not Save**.

## E17 Endianness

[Refer to RS485 and Modbus RTU settings for details.](/qr/fp-as310-english-v5/communication/rs485-setup.md)  <mark style="color:purple;">(Applicable to Model FP-AS310R)</mark>

| Options           | RS-485 Numbers | Remarks |
| ----------------- | -------------- | ------- |
| Big Endian        | 0              | Default |
| Little Endian     | 1              |         |
| Mid Big Endian    | 2              |         |
| Mid Little Endian | 3              |         |

After selecting a command, confirm whether to **Save** or **Not Save**.


---

# Agent Instructions: Querying This Documentation

If you need additional information that is not directly available in this page, you can query the documentation dynamically by asking a question.

Perform an HTTP GET request on the current page URL with the `ask` query parameter:

```
GET https://docs.lorric.com/qr/fp-as310-english-v5/parameters/e-commute.md?ask=<question>
```

The question should be specific, self-contained, and written in natural language.
The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.