D09 Total Trig.
Definition
Set the notification condition for the totalizer target. Default: Greater than target.
(D08 , D09 , and D10 work together to enable totalizer target alarm functionality.)
D08, D09, D10 Total Alarm Examples
Example 1: Forward Flow
Enable D08 Total Alarm.
Set D09 Total Trig. to “Greater Than”.
Set D10 Total Target to a positive value, e.g., +100.
When the cumulative forward flow exceeds 100,
the system triggers the total alarm.
Example 2: Reverse Flow
Enable D08 Total Alarm.
Set D09 Total Trig. to “Less Than”.
Set D10 Total Target to a negative value, e.g., -500.
When the cumulative reverse flow drops below -500,
the system triggers the total alarm.Notes
N/A
Operation Procedure
Button Functions (Click to Expand)
The main unit has four buttons. The bottom line (Line 3) of the LCD displays the current function of each button. Under normal operation, the button functions are as follows:
Blue Button: Leftmost button: Return, exit, or save settings.
Gray Direction Buttons:
Left Gray: Previous Page, decrease value, or select item
Right Gray: Next Page, increase value, or select item
Orange Button: Rightmost button: Enter settings, edit, or confirm selection
Do not hold buttons for extended periods to avoid damage.
Button functions may change depending on the operation context to improve usability or prevent accidental presses
Totalized Flow Alarm Function (Click to Expand)
This function triggers an alarm when the totalized flow reaches a value greater than or less than the preset target.
Related parameters: D08 Total Alarm, D09 Total Trigger Condition (Total Trig.), and D10 Total Target.
D08 Enable Totalizer Alarm
D08 Total Ala. Setting Steps:
• From the main screen (green backlight),
press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select D. Alarm & Info , press Orange Button (Enter).
• Use Gray Arrow Buttons to select D08 Total Ala. , press Orange Button (Enter).
• Use Gray Arrow Buttons to choose the options.
• Press Orange Button (Set) to confirm.
• Press Blue Button (ESC) to return to the main screen (green backlight).
D09 Set Total Trigger Condition
D09 Total Trig Setting Steps:
• From the main screen (green backlight),
press Orange Button (Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select D. Alarm & Info , press Orange Button (Enter).
• Use Gray Arrow Buttons to select D09 Total Trig , press Orange Button (Enter).
• Use Gray Arrow Buttons to choose the options.
• Press Orange Button (Set) to confirm.
• Press Blue Button (ESC) to return to the main screen (green backlight).
D10 Set Total Target Value
D10 Total Target Setting Steps:
• From the main screen(green backlight),
press Orange Button(Setup) to enter settings (orange backlight).
• Use Gray Arrow Buttons to select D. Alarm & Info, press Orange Button(Enter).
• Use Gray Arrow Buttons to select D10 Total Target, press Orange Button(Enter).
• Use Gray Arrow Buttons to choose the digit to adjust(highlighted in dark gray).
• Press Orange Button(Edit) to enter adjustment mode.
• Adjust digits: Left Gray Button to increase, Right Gray Button to decrease.
• Press Orange Button(Set) to confirm each digit; repeat for other digits as needed.
• After all digits are set, press Blue Button(Save).
• Confirm by pressing Orange Button(Save) (or Blue Button(NOT) to cancel).
• Press Blue Button(ESC) to return to the main screen(green backlight).
Totalizer Alarm Operation
When the totalizer alarm is enabled and the accumulated flow meets the trigger condition, the system triggers Alarm B. The alarm bits (Bit6, Bit7) are set to 1, indicating that the alarm is active.
The alarm behavior follows the mode set in D08:
ON: The receiving system receives the alarm signal, and the meter displays a red backlight alarm.
Do Not Disturb (DND): The receiving system still receives the alarm signal, but the meter does not display a red backlight alarm.
D09 Options, RS485 Values, Read/Write Commands, and Formats
Greater Than (Default)
-
0
Less Than
-
1
Last updated