D05 Up LIM
Definition
Set the upper limit of the normal flow range. Default: 100.
(D04 , D05 , D06 , and D07 work together to enable the flow range over-limit alarm function.)
Notes
If either D05 or D06 is adjusted, the other must also be set; otherwise, the display may not function correctly. If both are unset, default values are D05 = 100, D06 = 0.
DND Mode
When Do Not Disturb (DND) mode is enabled:
The flow meter detects abnormal conditions but the red backlight will not turn on. Example: Alarm-A “Paddle wheel abnormality” will not trigger the backlight in DND mode.
Abnormal conditions are still displayed on the Status/Alarm page.
If connected via RS485, the monitoring system still receives the alarm signal.
OCT alarm outputs continue to operate if configured.
Operation Procedure
D05 Options, RS485 Values, Read/Write Commands, and Formats
Default
100
-
Minimum
0
-
Maximum
100000
-