Parameters
Parameter categorizing table
Parameter Group
Name
Description
A
Measure
A group is about flow volume measurement
B
Unit
B group is about unit
C
Total & History
C group is about accumulated and history record
D
Alarm & Info(Alarm & Information)
D group is about alarm and notification.
E
Commute
E group adjust NPN 4-20mA and RS485
F
Simulate
F group is about simulation mode for communication and alarm testing.
H
System
H group is for system parameters, like brightness and reset.
Parameter description
A Measure parameter list
No.
Name
Description
A01
Pipe Type
Set the T-connector spec to use the correct calibration data. The default is 1 inch.
A02
Scales Factor
Sets the correction method for instantaneous flow by fine tuning flow volume in proportion. Default: 1.0
A04
Damping
Smooths flow reading by decreasing the fluctuation of measurement data, the lowest is 0, default value is 3 seconds.
A05
Direction
Set the displayed flow direction. Default: normal flow.
A09
Manual Offset
Corrects fixed errors that do not vary with flow (zero offset)
B Unit parameter list
No.
Name
Description
B01
Vol. Unit(Volume Unit)
Sets the flowmeter’s instantaneous flow volume unit. Default: L (liter).
B02
Time Unit
Sets the time unit for instantaneous flow. Default: minute.
B03
Total Unit(Total Volume Unit)
Sets the volume unit for cumulative and historical flow. Default: L (liter).
B05
Decimal Places
Sets the number of decimal places displayed on the LCD by using round down method. The maximum number of digits is 4 digits.Default: 04 (4 decimal place).Cumulative flow volume still calculated by using original value.
C Total & History parameter list
No.
Name
Description
C02
Del. Total (Delete Total)
Set the flow meter’s totalizer to zero manually. Default: No.
D Alarm & Information parameter list
No.
Name
Description
D01
Paddle Ala.(Paddle Alarm)
Set the flow meter’s alarm mode when module detect pipe diameter is abnormal. Default: Do Not Disturb. The alarm code belongs to Alarm – A.
D04
FlowLIM Ala (Flow Volume Limit Alarm)
Set the flow meter’s alarm mode for flow exceeding the instantaneous flow range. Default: Off. The alarm code belongs to Alarm – B.
D05
Up LIM(Upper Limit)
Set the upper limit of the normal flow range. Default: 100.
D06
Low LIM(Lower Limit)
Set the lower limit of the normal flow range. Default: 0.
D07
Hysteresis% (Hysteresis Percentage)
Set the hysteresis percentage for clearing flow upper and lower limit alarms. This ensures the alarm is only cleared when the flow stabilizes back within the set range. The percentage is defined relative to the span between the upper and lower limits. Default: 03 (3%).
D08
Total Ala.(Total Alarm)
Set the flow meter’s alarm mode for totalizer values exceeding the set range. Default: Off. The alarm code belongs to Alarm – B. (D08 , D9 , and D10 work together to enable totalizer target alarm functionality.)
D09
Total Trig.(Total Alarm Trigger Condition)
Set the notification condition for the totalizer target. Default: Greater than target.
D10
Total Target
Set up alarm target value of cumulative flow speed. Default: +100.
D13
PulseOverlap
Set the flow meter’s alarm mode for overlapping output signals caused by an excessively long E03 Pulse Width. The alarm code belongs to Alarm – B. (Only Applicable to Model FP-AS310A)
D14
IoutStatAlarm
Set the flow meter’s alarm mode for abnormal 4–20 mA current output (Iout). Default: Do Not Disturb. The alarm code belongs to Alarm – C. (Only Applicable to Model FP-AS310A)
E Commute parameter list
No.
Name
Description
E01
NC/NO
Sets whether the OCT output is open or closed when the condition is not met. The default setting is open.
(Only Applicable to Model FP-AS310A)
E02
OCT Info
Sets the definition for the flow meter’s OCT operation. Default: Off. (Only Applicable to Model FP-AS310A)
E03
Pulse Width
Sets the pulse width of the flow meter when E02 OCT Definition is set to “Pulse v2”. Default: 0.5 ms.
(Only Applicable to Model FP-AS310A)
E04
Modbus ID
Set up Modbus ID location, default 1.
(Only applicable to Model FP-AS310R)
E05
Baud
Sets the Modbus communication baud rate for the flow meter. The Master and Slave must use the same baud rate for communication. Default: Off. (Only applicable to Model FP-AS310R)
E06
Iout Def.(Iout Definition)
Sets the data to be output via the analog signal. The unit follows the setting in Parameter B (Unit Configuration). Default: Off. (Only Applicable to Model FP-AS310A)
E07
4mA Value
Set up corresponding value to 4mA, default 0. Both positive and negative values work. The value should be smaller than 20mA.
(Only Applicable to Model FP-AS310A)
E08
20mA Value
Set up corresponding value to 20mA, default 100. Both positive and negative values work. The value should be larger than 4mA.
(Only Applicable to Model FP-AS310A)
E11
4mA Adj. uA(4mA Output Adjustment in microAmp)
Fine-tunes the flow meter’s 4 mA output value. Unit: µA (microamperes). Default: 0.
(Only Applicable to Model FP-AS310A)
E12
20mA Adj. uA(20mA Output Adjustment in microAmp)
Fine-tunes the flow meter’s 20 mA output value. Unit: µA (microamperes). Default: 0. (Only Applicable to Model FP-AS310A)
E14
PulseV2 Unit
Defines the flow rate corresponding to one pulse output from the flow meter.
(Only Applicable to Model FP-AS310A)
E15
Byte format
Sets the data format for Modbus RTU communication. Default: N,8,1 (No parity, 8 data bits, 1 stop bit).
(Only applicable to Model FP-AS310R)
E16
Bit order
Sets the bit order for each byte during Modbus RTU transmission.
(Only applicable to Model FP-AS310R)
E17
Endianness
Sets the byte order for multi-byte data during RX (flow meter response) transmission.
(Only applicable to Model FP-AS310R)
F Simulate parameter list
No.
Name
Description
F01
Sim. Volume (Simulation Volume)
Sets the flow meter’s simulated instantaneous flow. The unit follows the setting in Category B. Default: +60.
F02
Sim. Mode (Simulation Mode)
Enables or disables the flow meter’s simulation mode. In simulation mode, the meter displays user-defined virtual flow values instead of actual sensor measurements. Default: Off.
F03
Sim. PulseHz (Simulation PulseHz)
Sets the simulated OCT pulse output frequency, in pulses per second (Hz). Range: 0–700. Default: 0.
(Applicable to Model FP-AS310A))
H System parameter list
No.
Name
Description
H02
LCD Bri.(LCD Brightness)
Set up brightness of LCD with 3 levels, default middle level.
H03
Green Light
Set up time of LCD green lighting with 3 durations, 10s, 60s, and always on.
H04
Language
Set up language. There are 2 languages:English, Traditional Chinese, default off.
H05
Paddle Init.(Paddle Initialization)
Press "Start" to initialize the paddle. User needs to rotate the paddle at least 20 rounds until the screen shows "Init. Succeed". If screens shows "Init. Failed", please try again. If the problem persists, please replace your paddle.
H06
Reset
Clear all the data (include date and cumulative data), reset all parameters to default values.
H07
Lock Device
Turn on the password function to prevent unauthorized access to the setting screen. The password can be changed in parameter H08, default off.
H08
Password
Modify the 4 digits password to prevent unauthorized access to the setting screen. The password function is enabled at parameter H07. The preset password is 0000.
H09
Engineer mode
H10
System Info
H11
Home Page