Set-up steps as below:
Connect cable according to the cable wiring section on this page.
This machine uses Modbus RTU protocol, communication parameter set-up as below.:
Set E04 for RS485 address, and please make sure there is no other device using the same address.
Set E05 for specifying communication Baud, this machine supports 9600, 19200, 38400 and 57600.
Please go back to the monitoring screen. RS485 only responses on monitoring screens.
If needed, please use F01 and F02 to set up the machine to do communication test under simulation mode.
Please refer to the Modbus RTU protocol page for testing the memory with read and write instruction.
Turn off F02 simulation mode.
Finish.