Please see the page of mechanical and electrical installation.
Please see the page of mechanical and electrical installation.
Please refer to the parameter set-up page.
Set-up steps as below:
Connect cable first according to the cable wiring section on this page.
Set up parameter E01 for selecting NC(Normal Close) or NO(Normal Open) when there is no signal.
Set up parameter E02 for specifying output signal content.
For selecting “pulse output”
Use E03 to confirm each pulse width.
Use F03 to simulate specific pulse output frequency at OCT for testing with external devices.
For selecting “out of range flow volume notice”.
Use D04 to turn on the alarm.
Use D05 D06 for specifying normal flow range.
Use D07 for specifying hysteresis range percentage. D07 is a positive value, it means the ranges single must exceed in order to disable the alarm.
Set up F01 and F02 for simulate flow volume and go back to the monitoring screen to confirm the alarm works
Turn off the simulation mode.
For selecting “Total Ala.” (“Inform of over total target”)
Use D08 to turn off alarm
Use D09 for specifying notification conditions. "Larger Than" is for positive flow direction, "Less Than" is for negative flow direction.
Use D10 for specifying total target, positive number is for positive flow, negative number is for negative flow.
Set up F01 and F02 to simulate flow volume and go back to the monitoring screen to confirm the alarm works.
Turn off the simulation mode.
Go back to the monitoring screen, finish.
Pulse output is based on the frequency of the paddle wheel’s revolutions. Due to not adapting LORRIC’s data processing technology, it is only applicable to the environment without high precision request. A pulse will be sent by every 180° revolution. To calculate the total flow volume for a certain period of time, count the number of pulse signals received then divided by the corresponding K-value this manual provides. K value is defined by pipe size and material. Please refer to T-connector page.
Please see the page of mechanical and electrical installation.
Please see the page of mechanical and electrical installation.
Please refer to parameter set-up page.
Set-up steps as below:
Connect cable according to the cable wiring section on this page.
This machine uses Modbus RTU protocol, communication parameter set-up as below.:
Set E04 for RS485 address, and please make sure there is no other device using the same address.
Set E05 for specifying communication Baud, this machine supports 9600, 19200, 38400 and 57600.
Please go back to the monitoring screen. RS485 only responses on monitoring screens.
If needed, please use F01 and F02 to set up the machine to do communication test under simulation mode.
Please refer to the Modbus RTU protocol page for testing the memory with read and write instruction.
Turn off F02 simulation mode.
Finish.
Please see the page of mechanical and electrical installation.
Please see the page of mechanical and electrical installation.
Please refer to the parameter set-up page.
Set-up steps as below:
Connect cable first according to the cable wiring section on this page.
Set up parameter E06 for selecting the data to output.
Parameter E07 and E08 are for specifying maximum and minimum value to output. These 2 values can be either positive or negative, however, E07 has to be smaller than E08.
Use E09 to set output current milliamps when output data is out of the E07 and E08 range, there are 3 options:
"2.4 & 21.6" stands for outputting 2.4mA when data is less than E07 value, and outputting 21.6mA when data is greater than E08 value.
"2.4" stands for outputting 2.4mA when data is less than E07 value and greater than E08 value.
"21.6" stands for outputting 2.4mA when data is less than E07 value and greater than E08 value.
Turn on F02.
Please enter the E11 parameter page to test and adjust 4mA output current. Adjustment unit is uA.
Please enter the E12 parameter page to test and adjust 20mA output current. Adjustment unit is uA..
If the output current is too low and can not reach 20mA after adjustment, please check the electrical installation page for line impedance and supply voltage requirement.
Turn off F02 and go back to the monitoring screen.
Finish.
This instruction if for memory with 2 register length only, please refer to the list.
Format of command (30) from master
Description of master command
This example will change A02 Scale Factor value to 2.50
slave address: 01(address of this flowmeter)
function code: 30(double Register write instruction)
Address of first reading register: 0001(memory address to write)
Write data: 40 20 00 00 (Change A02 Scale Factor value to 2.50)
CRC: 98 0E (Calculating error correcting code according to CRC algorithm)
Format of flowmeter response(30)
Description of flowmeter response example
Valid command received. It will output the same command back to master.
slave address: 01(address of this flowmeter)
function code: 30(double Register write instruction)
Address of first reading register: 0001(memory address to write)
Write data: 40 20 00 00 (Change A02 Scale Factor value to 2.50)
CRC: 98 0E (Calculating error correcting code according to CRC algorithm)
Format of command (04) from master
Description of master command
The example will read instantaneous flow volume.
slave address: 01(address of this flowmeter)
function code: 04(read instruction)
Address of first reading register: 0000(Address of first register to read)
Quantity of registers to be read: 0002 (need to read 2 registers from 0000)
CRC: 71 CB(Calculating error correcting code according to CRC algorithm)
Description of flowmeter response example
slave address: 01(address of this flowmeter)
function code: 04(read instruction)
Amount of response Byte: 04 (2 register=4 byte)
Data Byte: 00 00 00 00(Assume the instantaneous flow volume is 0)
CRC: FB 84(Calculating error correcting code according to CRC algorithm)
How to use these charts
Read-only memory list
bit order: lsb first
byte order: big endian
Data bits:8
Parity: None
Stop bits: 1
Floating point number follows IEEE754-1985. The float32 below stands for 32bits Single precision floating point number.
Register: Length of 2 Byte or 16bit which is unit length of memory in Modbus RTU.
Byte: 8 bit length
Modbus memory is divided into two categories, read-only and read-write.
Read-only type is mainly for flow meter status related memory, such as instantaneous flow rate. This is also the most commonly used memory. Detail information in following page:
Read-write memory is mainly to set-up parameters such as pipe diameter, and to reset variables, such as set zero on the cumulative flow. Read-write memory is only readable by using instruction 03. You can only change one parameter at a time with the write operation. If the length of the target register is 1, please use instruction 06. If the length is 2 registers, please use instruction 30. Please see read-write memory detail page below:
Read-write memory instruction detail information as below:
Register location
Memory definition
Data type
0001
scale factor
float 32
0304
upper limit
float 32
0306
lower limit
float 32
030B
Total Target
float 32
0406
4mA Value
float 32
0408
20mA Value
float 32
040B
4mA Adjust
float 32
040D
20mA Adjust
float 32
Byte#
1
2
3
4
5
6
7
8
9
10
Node ID
Slave Address
Function Code
Memory address to write
Memory address to write
Write data
Write data
Write data
Write data
CRC
CRC
Example
01~FF
01
30
00
01
40
20
00
00
98
0E
Byte#
1
2
3
4
5
6
7
8
9
10
Node ID
Slave Address
Function Code
Memory address to write
Memory address to write
Write data
Write data
Write data
Write data
CRC
CRC
Example 01~FF
01
30
00
01
40
20
00
00
98
0E
Byte# | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Node ID | Slave Address | Function Code | Address of first reading register | Address of first reading register | Quantity of registers to be read | Quantity of registers to be read | CRC | CRC |
Example 01~FF | 01 | 04 | 00 | 00 | 00 | 02 | 71 | CB |
Byte# | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
Node ID | Slave Address | Function Code | Amount of response Byte | Data Byte #1 | Data Byte #2 | Data Byte #3 | Data Byte #4 | CRC | CRC |
Example 01~FF | 01 | 04 | 04 | 00 | 00 | 00 | 00 | FB | 84 |
Read-write memory type | Function |
Register location | Read-write memory address is not shared with read-only memory. |
Register length | The length of variable memory. The unit is Register(2Byte). |
Memory definition | For memory data description. |
Data type | The format of sending and receiving data type. |
Read-write memory type | Function |
Register location | Read-write memory address is not shared with read-only memory. |
Register length | The length of variable memory. The unit is Register(2Byte). |
Memory definition | For memory data description. |
Data type | The format of sending and receiving data type. |
Read-write function | R stands for readable, W stands for writable. Some memories are write-only. |
Register location | Register length | Memory definition | Data type | Read-write function | Remarks |
A group parameters |
0000 | 1 | pipe type | unsigned int 16 | R/W | Multiple choice parameter type |
0001 | 2 | scale factor | float 32 | R/W |
0003 | 1 | anti noise | unsigned int 16 | R/W | Multiple choice parameter type |
0004 | 1 | damping | unsigned int 16 | R/W |
0005 | 1 | direction | unsigned int 16 | R/W | Multiple choice parameter type |
0006 | 1 | neg flow | unsigned int 16 | R/W | Multiple choice parameter type |
0007 | 1 | ext mode | unsigned int 16 | R/W | Multiple choice parameter type |
B group parameters |
0100 | 1 | vol unit | unsigned int 16 | R/W | Multiple choice parameter type |
0101 | 1 | time unit | unsigned int 16 | R/W | Multiple choice parameter type |
0102 | 1 | total unit | unsigned int 16 | R/W | Multiple choice parameter type |
0103 | 1 | speed unit | unsigned int 16 | R/W | Multiple choice parameter type |
C group parameters |
0200 | 1 | total method | unsigned int 16 | R/W | Multiple choice parameter type |
0201 | 1 | clear total | unsigned int 16 | W |
0202 | 1 | history function | unsigned int 16 | R/W | Multiple choice parameter type |
0203 | 1 | clear history | unsigned int 16 | W |
D group parameters |
0300 | 1 | paddle alarm | unsigned int 16 | R/W | Multiple choice parameter type |
0301 | 1 | magnetic alarm | unsigned int 16 | R/W | Multiple choice parameter type |
0302 | 1 | battery alarm | unsigned int 16 | R/W | Multiple choice parameter type |
0303 | 1 | flow limit alarm | unsigned int 16 | R/W | Multiple choice parameter type |
0304 | 2 | upper limit | float 32 | R/W |
0306 | 2 | lower limit | float 32 | R/W |
0308 | 1 | hyster value | unsigned int 16 | R/W |
0309 | 1 | total alram | unsigned int 16 | R/W | Multiple choice parameter type |
030A | 1 | total trigger | unsigned int 16 | R/W | Multiple choice parameter type |
030B | 2 | total target | float 32 | R/W |
030D | 1 | iout alarm | unsigned int 16 | R/W | Multiple choice parameter type |
030E | 1 | velocity alarm | unsigned int 16 | R/W | Multiple choice parameter type |
030F | 1 | slow pulse alarm | unsigned int 16 | R/W | Multiple choice parameter type |
E group parameters |
0400 | 1 | nc no | unsigned int 16 | R/W | Multiple choice parameter type |
0401 | 1 | oct info | unsigned int 16 | R/W | Multiple choice parameter type |
0402 | 1 | pulse width | unsigned int 16 | R/W | Multiple choice parameter type |
0403 | 1 | modbus address | unsigned int 16 | R/W |
0404 | 1 | modbus baud | unsigned int 16 | R/W | Multiple choice parameter type |
0405 | 1 | iout definition | unsigned int 16 | R/W | Multiple choice parameter type |
0406 | 2 | 4mA value | float 32 | R/W |
0408 | 2 | 20mA value | float 32 | R/W |
040A | 1 | iout error | unsigned int 16 | R/W | Multiple choice parameter type |
040B | 2 | 4mA adj | float 32 | R/W |
040D | 2 | 20mA adj | float 32 | R/W |
F group parameters |
0500 | 2 | sim rate | float 32 | R/W |
0502 | 1 | sim on - reserved | const | R |
0503 | 1 | sim pulse - reserved | const | R |
G group parameters |
0600 | 1 | set year*1 | unsigned int 16 | R/W |
0601 | 1 | set month*1 | unsigned int 16 | R/W |
0602 | 1 | set day*1 | unsigned int 16 | R/W |
0603 | 1 | set time*2 | unsigned int 16 | R/W |
0604 | 1 | date format | unsigned int 16 | R/W | Multiple choice parameter type |
H group parameters |
0700 | 1 | led brightness | unsigned int 16 | R/W | Multiple choice parameter type |
0701 | 1 | lcd brightness | unsigned int 16 | R/W | Multiple choice parameter type |
0702 | 1 | green light | unsigned int 16 | R/W | Multiple choice parameter type |
0703 | 1 | lang | unsigned int 16 | R/W |
0704 | 1 | paddle init | unsigned int 16 | W |
0705 | 1 | reset | unsigned int 16 | W |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0000 | pipe type | 0 | 1 inch PVC T-connector |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0003 | anti noise | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0005 | direction | 0 | normal |
1 | inverse |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0006 | neg flow | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0007 | ext mode | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0100 | vol unit | 0 | L |
1 | m3 |
2 | us gal |
3 | imp gal |
4 | ft3 |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0101 | time unit | 0 | second |
1 | minute |
2 | hour |
3 | day |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0102 | total unit | 0 | L |
1 | m3 |
2 | us gal |
3 | imp gal |
4 | ft3 |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0103 | speed unit | 0 | m/s |
1 | ft/s |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0200 | total method | 0 | pos |
1 | neg |
2 | net |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0202 | history function | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0300 | paddle alarm | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0301 | magnetic alarm | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0302 | battery alarm | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0303 | flow limit alarm | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0309 | total alarm | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
030A | total trigger | 0 | higher than target |
1 | lower than target |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
030D | iout alarm | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
030E | velocity alarm | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
030F | slow pulse alarm | 0 | off |
1 | on |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0400 | nc no | 0 | nc |
1 | no |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0401 | oct info | 0 | alarm a |
1 | alarm a b |
2 | alarm a b c |
3 | over flow volume |
4 | over total |
5 | paddle pulse |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0402 | pulse width | 0 | 0.5ms |
1 | 1ms |
2 | 10ms |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0404 | modbus baud | 0 | 9600 |
1 | 19200 |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0405 | iout definition | 0 | flow volume |
1 | velocity |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
040A | iout error | 0 | 2.4 mA & 21.6 mA |
1 | 2.4 mA |
2 | 21.6 mA |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0604 | date format | 0 | yyyy-mm-dd |
1 | yyyy/mm/dd |
2 | dd/mm/yyyy |
3 | mm/dd yy |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0700 | led brightness | 0 | low |
1 | medium |
2 | high |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0701 | lcd brightness | 0 | low |
1 | medium |
2 | high |
Memory address | Memory definition | unsigned int 16 value | Corresponding option | Remarks |
0702 | green light | 0 | always on |
1 | 10 seconds |
2 | 60 seconds |
Register location | Register length | Memory definition | Data type | Remarks |
0000 | 2 | instantaneous flow rate | float 32 |
0002 | 2 | instantaneous flow velocity | float 32 |
0004 | 2 | totalized flow volume | float 32 |
0006 | 2 | analog output in micro-amp | unsigned int 32 |
0008 | 1 | unsigned int 16 | First byte is 0, due to no definition. |
0009 | 1 | unsigned int 16 | First byte is 0, due to no definition. |
000A | 1 | unsigned int 16 | First byte is 0, due to no definition. |
000B | 1 | unsigned int 16 | First byte is 0, due to no definition. |
000C | 1 | unsigned int 16 | First byte is 0, due to no definition. |
000D | 1 | history[1] year & month | unsigned int 16 |
000E | 1 | history[1] day | unsigned int 16 |
000F | 1 | history[1] total method | unsigned int 16 |
0010 | 2 | history[1] totalized flow volume | float32 |
0012 | 1 | history[2] year & month | unsigned int 16 |
0013 | 1 | history[2] day | unsigned int 16 |
0014 | 1 | history[2] total method | unsigned int 16 |
0015 | 2 | history[2] totalized flow volume | float32 |
0017 | 1 | history[3] year & month | unsigned int 16 |
0018 | 1 | history[3] day | unsigned int 16 |
0019 | 1 | history[3] total method | unsigned int 16 |
001A | 2 | history[3] totalized flow volume | float32 |
001C | 1 | history[4] year & month | unsigned int 16 |
001D | 1 | history[4] day | unsigned int 16 |
001E | 1 | history[4] total method | unsigned int 16 |
001F | 2 | history[4] totalized flow volume | float32 |
0021 | 1 | history[5] year & month | unsigned int 16 |
0022 | 1 | history[5] day | unsigned int 16 |
0023 | 1 | history[5]total method | unsigned int 16 |
0024 | 2 | history[5] totalized flow volume | float32 |
0026 | 1 | history[6] year & month | unsigned int 16 |
0027 | 1 | history[6] day | unsigned int 16 |
0028 | 1 | history[6] total method | unsigned int 16 |
0029 | 2 | history[6] totalized flow volume | float32 |
002B | 1 | history[7] year & month | unsigned int 16 |
002C | 1 | history[7] day | unsigned int 16 |
002D | 1 | history[7] total method | unsigned int 16 |
002E | 2 | history[7] totalized flow volume | float32 |
0030 | 1 | history[8] year & month | unsigned int 16 |
0031 | 1 | history[8] day | unsigned int 16 |
0032 | 1 | history[8] total method | unsigned int 16 |
0033 | 2 | history[8] totalized flow rate | float32 |
0035 | 1 | history[9] year & month | unsigned int 16 |
0036 | 1 | history[9] day | unsigned int 16 |
0037 | 1 | history[9] total method | unsigned int 16 |
0038 | 2 | history[9] totalized flow rate | float32 |
003A | 1 | history[10] year & month | unsigned int 16 |
003B | 1 | history[10] day | unsigned int 16 |
003C | 1 | history[10] total method | unsigned int 16 |
003D | 2 | history[10] totalized flow rate | float32 |
003F | 1 | history[11] year & month | unsigned int 16 |
0040 | 1 | history[11] day | unsigned int 16 |
0041 | 1 | history[11] total method | unsigned int 16 |
0042 | 2 | history[11] totalized flow rate | float32 |
0044 | 1 | history[12] year & month | unsigned int 16 |
0045 | 1 | history[12] day | unsigned int 16 |
0046 | 1 | history[12] total method | unsigned int 16 |
0047 | 2 | history[12] totalized flow rate | float32 |
0049 | 1 | history[13] year & month | unsigned int 16 |
004A | 1 | history[13] day | unsigned int 16 |
004B | 1 | history[13] total method | unsigned int 16 |
004C | 2 | history[13] totalized flow rate | float32 |
004E | 1 | history[14] year & month | unsigned int 16 |
004F | 1 | history[14] day | unsigned int 16 |
0050 | 1 | history[14] total method | unsigned int 16 |
0051 | 2 | history[14] totalized flow rate | float32 |
This instruction if for memory with 1 register length only, please refer to the list.
Format of command (06) from master
Description of master command
This example will change A01 pipe diameter option
slave address: 01(address of this flowmeter)
function code: 06(Single Register write instruction)
Address of first reading register: 0000(memory address to write)
Write data: 0000 (1" PVC pipe)
CRC: C40B (Calculating error correcting code according to CRC algorithm)
Format of flowmeter response(06)
Description of flowmeter response example
Valid command received. It will output the same command back to master.
slave address: 01(address of this flowmeter)
function code: 06(Single Register write instruction)
Address of first reading register: 0000(memory address to write)
Write data: 0000 (1" PVC pipe)
CRC: C40B (Calculating error correcting code according to CRC algorithm)
Format of command (03) from master
Description of master command
The example will read A01 pipe diameter options and A02 Scale Factor.
slave address: 01(address of this flowmeter)
function code: 03(read instruction)
Address of first reading register: 0000(Address of first register to read)
Quantity of registers to be read: 0003 (need to read 2 registers from 0000)
CRC: 05 CB (Calculating error correcting code according to CRC algorithm)
Format of flowmeter response(03)
Description of flowmeter response example
slave address: 01(address of this flowmeter)
function code: 03(read instruction)
Amount of response Byte: 06 (3 register=6byte)
Data Byte:
00 00(Current pipe diameter is 1inch PVC)
3F 80 00 00(Current Scale Factor is 1.0)
CRC: 2C 89 (Calculating error correcting code according to CRC algorithm)
Byte#
1
2
3
4
5
6
7
8
Node ID
Slave Address
Function Code
Memory address to write
Memory address to write
Write data
Write data
CRC
CRC
Example
01~FF
01
06
00
00
00
01
48
0A
Byte#
1
2
3
4
5
6
7
8
Node ID
Slave Address
Function Code
Memory address to write
Memory address to write
Write data
Write data
CRC
CRC
Example
01~FF
01
06
00
00
00
01
48
0A
Byte#
1
2
3
4
5
6
7
8
Node ID
Slave Address
Function Code
Address of first reading register
Address of first reading register
Quantity of registers to be read
Quantity of registers to be read
CRC
CRC
Example 01~FF
01
03
00
00
00
03
05
CB
Byte#
1
2
3
4
5
6
7
8
9
10
11
Node ID
Slave Address
Function Code
Amount of response Byte
Data Byte #1
Data Byte
#2
Data Byte
#3
Data Byte
#4
Data Byte #5
Data Byte
#6
CRC
CRC
Example
01~FF
01
03
06
00
00
3F
80
00
00
2C
89